WA14 Spec Sheet
Electrical and Physical Data
WA14 Series
WeatherKing 5
Physical Data
Model No.
WA1418A
WA1424C
WA1430B
WA1436B
WA1442C
WA1448B
WA1460A
Nominal Tonnage
1.5
2.0
2.5
3.0
3.5
4.0
5.0
Valve Connections
Liquid Line O.D. – in.
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Suction Line O.D. – in.
5/8
3/4
3/4
3/4
7/8
7/8
7/8
Refrigerant (R410A) furnished oz.¹
82
85
98
122
135
146
228
Compressor Type
Scroll
Outdoor Coil
Net face area – Outer Coil
11.1
13.7
13.7
18.3
18.3
21.9
21.9
Net face area – Inner Coil
—
—
—
— — —
—
Tube diameter – in.
0.375
3/8
3/8
3/8
3/8
3/8
3/8
Number of rows
1
1
1
1
1
1
2
Fins per inch
22
22
22
22
22
22
22
Outdoor Fan
Diameter – in.
18
22
22
22
22
24
24
Number of blades
2
2
2
2
3
3
3
Motor hp
1/10
1/12
1/8
1/5
1/4
1/5
1/3
CFM
1697
2077
2121
2702
3174
3571
3360
RPM
1100
841
1075
819
1075
850
1085
watts
108
76
155
149
244
235
311
Shipping weight – lbs.
135
171
144.5
166
184
225
274
Operating weight – lbs.
128
164
137.5
159
176
205
254
Electrical Data
Line Voltage Data (Volts-Phase-Hz)
208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Maximum overcurrent protection (amps)²
20 25 25 30 35 45 60
Minimum circuit ampacity³
13 15 17 19 23 26 35
Compressor
Rated load amps
9.7 11.2 12.8 14.1 16.7 19.9 26.4
Locked rotor amps
46 60.8 64 77 109 109 134
Condenser Fan Motor
Full load amps
0.5 .36 0.7 1.2 1.3 1 1.7
Locked rotor amps
1.3 1 1.2 2 2.5 2.3 3.2
¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instrucitons for information about set length and
additional refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Electrical and Physical Data