Technical data
C6501000 F3-F5 I-O manual Rev4_3 9
APPLICATION FIELD WIRING
WIRING DIAGRAM SHOWN BELOW FOR STANDARD RIELLO 530 SE/C PRIMARY CONTROL BOX
INSTALLATION NOTE: ELECTRONIC AIR SHUTTER REQUIRES A CONSTANT 120V POWER
SUPPLY TO THE AUX TERMINAL, FAILURE TO PROVIDE THIS WILL RESULT IN NO BURNER
OPERATION OR AIR SHUTTER WILL NOT CLOSE.
WARNING: DO NOT activate burner until proper oil line connections have been made, or
failure of the pump shaft seal may occur.
WARNING: DO NOT activate burner until all safety and operating controls have been
wired in series with the burner, as required by local code authorities and/or as specified by
the appliance manufacturer.
RECOMMENDED FIELD WIRING FOR
TYPICAL APPLICATIONS
120VAC 60HZ.
LN
AUX
N L
AIR
SHUTTER
MOTOR.
120V OPERATED SYSTEMS 24V OPERATED SYSTEMS
3
6
2
4
1
5
120VAC 60HZ.
LN
AUX
N L
AIR
SHUTTER
MOTOR.
t °
T
T
24V SWITCHING
RELAY
2
4
3
6
1
5
WIRING LEGEND:
PLEASE NOTE: OPERATING LIMIT AND SAFETY LIMIT ARE TWO SEPARATE LIMITS .
(1) MAIN DISCONNECT FUSE
(2) MANUAL SERVICE SWITCH
(3) "SAFETY" LIMIT DEVICE
(4) "OPERATING" LIMIT DEVICE
(5) EARTH GROUND CONNECTION BURNER CHASSIS
(6) BURNER CONTROL REMOTE LOCK OUT ALARM DEVICE - WIRED & SUPPLIED BY OTHERS.
(AUX) AUXILIARY SUB BASE ADD-ON CONNECTOR (AIR SHUTTER)
(T - T) 24V THERMOSTAT CONNECTIONS - LOW VOLTAGE OPERATED SYSTEMS
MIN. WIRE SIZE:
INSULATED 18 AWG SOLID OR 16 STRD.
RATED 105° C
PROPER EARTH GROUNDING MEANS REQ.'D
ALL WIRING SHOWN PROVIDED BY OTHERS