Technical data

C6501000 F3-F5 I-O manual Rev4_3 17
RIELLO 40 SERIES OIL BURNER EQUIPPED WITH ELECTRIC AIR
SHUTTER NO FLAME OPERATIONAL SEQUENCE
CALL FOR
HEAT
STANDY BY
ELECTRIC AIR SHUTTER CLOSED ~ WAITING FOR CALL FOR HEAT
MOTOR /
PREPURGE
IGNITION
OIL VALVE
FLAME
POWER
LOCK OUT
THERMOSTAT OR LIMIT CONTROL ELECTRIC AIR SHUTTER MODES
40 SERIES OIL BURNER MODES
CONSTANT UNITERUPTED 120V POWER SUPPLY
TO ELECTRIC AIR SHUTTER ASSEMBLY
AIR
SHUTTER
ELECTRIC AIR SHUTTER OPENS ~ ONCE FULLY OPEN SWITCHES POWER TO BURNER MOTOR
AIR
SHUTTER
BURNER MOTOR STOPS ~ ELECTRIC AIR SHUTTER CLOSES
open
AC
closed
X
RIELLO 40 SERIES OIL BURNER EQUIPPED WITH ELECTRONIC AIR
SHUTTER NORMAL OPERATIONAL SEQUENCE
CALL FOR
HEAT
STANDY BY
ELECTRIC AIR SHUTTER CLOSED ~ WAITING FOR CALL FOR HEAT
MOTOR /
PREPURGE
IGNITION
OIL VALVE
FLAME
POWER
HEAT
SATISFIED
THERMOSTAT OR LIMIT CONTROL ELECTRIC AIR SHUTTER MODES
40 SERIES OIL BURNER MODES
CONSTANT UNITERUPTED 120V POWER SUPPLY
TO ELECTRIC AIR SHUTTER ASSEMBLY
AIR
SHUTTER
ELECTRIC AIR SHUTTER OPENS ~ ONCE FULLY OPEN SWITCHES POWER TO BURNER MOTOR
AIR
SHUTTER
BURNER MOTOR STOPS ~ ELECTRIC AIR SHUTTER CLOSES
open
AC
closed