TECHNICAL SPECIFICATIONS SPECIFICHE TECNICHE DIALOG PLUS 700-3000VA SINGLE-PHASE On line double conversion (VFI) technology SPEDLPX0205REN
DIALOG PLUS Table of contents ..1.. OBJECTIVE 3 ..2.. DESCRIPTION OF THE SYSTEM 3 ..3.. APPLICATIONS 4 ..4.. CHARACTERISTICS 4 ..5.. NORMATIVE REFERENCES 7 > 5.1 Main reference standards > 5.2 Standards relating to systems and installation 7 8 ..6.. SUPPLIED EQUIPMENTS AND ACCESSORIES 9 > 6.1 Tower version > 6.2 Rack version 9 10 ..7.. BLOCK DIAGRAM 11 > 7.1 Block diagram of the UPS > 7.2 Options 11 11 ..8.. INTERFACING 15 > 8.1 Serial communication port > 8.
DIALOG PLUS 1 - OBJECTIVE This technical document has been produced to be used by UPS system designers and installers. The objective of this document is to provide and illustrate: . the technical information required to enable you to choose the correct UPS to suit your needs . the information required to set up and configure the system . the information concerning the installation and location of the UPS .
DIALOG PLUS Rack version MODEL Nominal power Nominal output voltage [VA] Dialog Plus rack 100 / 100 ER 1000 [Vac] Dimensions WxDxH (1) [mm] Weight [Kg] (1) Dialog Plus rack 70 700 Dialog Plus rack 150 1500 Dialog Plus Dialog Plus rack rack 220 / 220 ER 300 / 300 ER 2200 3000 220 / 230 / 240 483x390x88 483x390x88 13 483x480x88 16 / 9 21 483x480x176 483x480x176 / 483x480x88 / 483x480x88 38 / 13 39 / 14 Note: 88mm = 2U; 176mm = 4U (2U + 2U); 483mm = 19” 3 - APPLICATIONS => Personal computers
DIALOG PLUS − Programmable timer: This function enables the user to program the timer to automatically switch the system on or off at specific times (configurable via the software). − Stand by: During Stand-by function the inverter is switched off and the batteries are charged. The stand-by function is automatically activated when the UPS is switched off.
DIALOG PLUS Battery optimisation − High level of battery reliability (automatic battery test): The UPS carries out battery tests automatically; these tests enable the system to periodically check the efficiency of the batteries in order to prevent any faults occurring to them. The test does not in any way compromise the supply to the connected equipment, and given the short duration (seconds), it does not affect the life or the back-up time of the batteries.
DIALOG PLUS Windows 95, 98, 2000, Windows 2003 Server, Me, Xp, NT4.0, Novell, Mac OS, Mac Osx, Mac Os 9.x & Linux operating systems. The software enables the user to programme the automatic start-up and shutdown of the system on a weekly basis. The UPS also contains the following hardware interfaces: − RS232 serial port − signals interface − slot for the installation of various adaptors 5 - NORMATIVE REFERENCES > 5.
DIALOG PLUS IEC61000-4-11: EN50141: EN55022: Low frequency disturbances Induced radio interference Radio frequency disturbance ENV62040-3 Uninterruptible power supply systems (UPS): performance provisions and test procedures. IEC146 (CEI22): Semiconductor electronic converters IEC529 (CEI70-1): Degree of protection of casings European Directives 73/23 Low voltage directive enforcing the obligatory CE marking from 1/1/97. This directive concerns all safety issues associated with the equipment.
DIALOG PLUS 6 - SUPPLIED EQUIPMENT AND ACCESSORIES > 6.
DIALOG PLUS > 6.
DIALOG PLUS 7 - BLOCK DIAGRAM > 7.1 Block diagram of the UPS > 7.2 Options Isolating transformer Battery back-up extension Remote led mimic panel Net Adapter USB Converter Multiplexer LEGEND: 1) Re-settable input protection 2) Input EMI filter + back-feed protection: Input filter for protecting the UPS and load against any electromagnetic disturbances.
DIALOG PLUS 4) Rectifier/Booster: When the mains power supply is present, this converts the mains alternating current (AC) into a direct current (DC) whilst controlling the power factor. If the mains power supply fails, it increases the voltage from the battery to an appropriate voltage level to power the inverter stage.
DIALOG PLUS Operating modes "NORMAL" mode During NORMAL mode, the UPS power is taken from the incoming mains supply, whilst the UPS output (load) is supplied by the inverter (refer to the block diagram), and the batteries are maintained at a fully charged state. Automatic "BY PASS" mode The UPS will switch to BYPASS mode in the event of one of the following scenarios: a) Immediately after the UPS is switched on if the mains power supply is present.
DIALOG PLUS “Mains out of tolerance” The UPS is designed to function with a wide range of input voltages. This ensures that the batteries do not intervene unnecessarily, thus increasing the back-up time should an actual blackout occur. The microprocessor continuously checks the input voltage and frequency to ensure a high standard of operation and will switch the load onto the by-pass within a wide tolerance range.
DIALOG PLUS 8 - INTERFACING > 8.1 Serial communication port The UPS has the following communication ports (see UPS views): - RS232 serial port - COMMUNICATION SLOT: expansion slot for additional interface cards RS232 serial port The RS232 serial port enables the connection of a PC (COM port) by means of a pin-to-pin serial cable (provided(1)). RS232 CONNECTOR 6 7 8 9 1 2 3 4 5 PIN No.
DIALOG PLUS > 8.2 Communication software MAIN CHARACTERISTICS 1) Sequential and prioritised shutdown: PowerShield2 enables the user to shutdown the network without having to individually switch off each PC or server, and before doing so, Powershield² will save the work that was being done regardless of the application that was being used. The user may also define their own shutdown procedure and also prioritise the shutdown of critical components within the system (such as vital and non vital servers).
DIALOG PLUS POWERSHIELD2 SOFTWARE FUNCTIONS 1) Graphical monitoring of the UPS status PowerShield2 is the easy to use yet powerful program that enables the user to monitor and control the UPS systems. There are various graphical versions including Windows, Java, OS/2 and MacOS. 2) MACOS version The PowerShield2 software is the only UPS control and shutdown software available for the Macintosh that has a client-server architecture.
DIALOG PLUS > 8.3 Configuration software Configuration Software UPSTools software enables the user to configure the UPS, and provides a full view of the system parameters and status through the RS232 serial port. Refer to the paragraph UPS Configuration for a list of the configurable values available. UPS Configuration The following table lists all of the possible configurable values available so as to best adapt the UPS to the user requirements.
DIALOG PLUS 9 - OPTIONS > 9.1 Summary table of the options available DESCRIPTION Isolating transformer module for DLP 100/DLP 150 Isolating transformer module for DLP200/DLP300 PowerShield2 communication software (“full” version) Remote display panel with led DIMENSIONS (HxWxD mm) WEIGHT ( KG ) 480x158x348 22 480x158x348 30 ISOLATING TRANSFORMER MODULE: Enables the UPS output to be galvanically isolated from the input.
DIALOG PLUS 10 - FRONT PANEL > 10.1. Display panel The LED display panel enables the user to check the UPS status and operating mode. It indicates in which mode the UPS is working (on mains, on by-pass, on battery); it shows the load applied; the battery charge level and warns of any error conditions occurring.
DIALOG PLUS Green / Steady The UPS is operating in battery mode and the audible alarm will sound at regular intervals. Green / Flashing When operating from battery power, the UPS will signal that it is about to switch off due to the end of discharge.
DIALOG PLUS Table 3: input voltage Input Voltage 190V~200V 200V~230V 230V~250V 250V~260V >260V 1 * * * * * 2 Battery LED bar 3 4 5 * * * * * * * * * * 100 ! Table 4: load level Load level Load LED bar 25 50 75 0~5% * 5~25% * 25%~50% * * 50%~75% * * * 75%~102% * * * * >102% * * * * * LED illuminated steady Overloads on the UPS The following table shows how the UPS reacts when overloads occur during mains or battery operation, and indicates the time that the UPS will con
DIALOG PLUS > 10.3 UPS front view Dialog Plus 700 - 1000 - 1500VA Dialog Plus 2000 - 3000VA 1. LED mimic panel 2. ON button 3.
DIALOG PLUS 11 - REAR PANEL > 11.1 Rear panel 700 – 2000 VA Models Dialog Plus 700VA 1 Dialog Plus 1000-1000ER-1500VA 7 1 7 8 2 2 3 6 3 4 4 5 5 6 Dialog Plus 2000VA 1 7 8 2 6 4 3 5 1. 2. 3. 4. RS232 serial communication port Cooling fans Telephone/modem protection/net or intranet Input thermal re-settable protection 5. 6. 7. 8.
DIALOG PLUS > 11.2 Rear panel 2000ER – 3000/3000ER VA Models Dialog Plus 2000 ER VA 1 Dialog Plus 3000 / 3000 ER VA 1 7 7 8 8 9 2 2 6 10 6 3 4 5 3 4 5 1. 2. 3. 4. 5. RS232 serial communication port Cooling fans Telephone/modem protection/net or intranet Input thermal re-settable protection IEC mains input plug 6. IEC output sockets (max 10A) 7. Communication expansion slot 8. Battery expansion connector 9. IEC 16A output socket 10.
DIALOG PLUS 12 TECHNICAL DATA > 12.
DIALOG PLUS > 12.3 Summary data sheets MODEL Input phases Rated voltage Maximum input voltage before battery intervention Minimum input voltage before battery intervention (applied load 100%) Rated frequency Input frequency tolerance Maximum current In-rush current 700VA 1000VA 1000VA ER 1500VA INPUT 3000VA 3000VA ER 14.4 A 16 A 300 V single phase (110 ± 5) V single phase (load 0% - 60%) (160±5) V single phase (load 80% - 100 %) 3.
DIALOG PLUS MODEL 700VA 1000VA Back-up in minutes No.
DIALOG PLUS MODEL Frequency variation velocity (Hz/sec.
DIALOG PLUS MODEL Depth (mm) Weight in Kg (with standard back-up integrated batteries) Mechanical characteristics Level of protection Resistance to vibrations (G) Power dissipated with load present (W) Colour 700VA 400 1000VA 400 1000VA ER 400 1500VA 500 2000VA 460 2000VA ER 460 3000VA 460 3000VA ER 460 12 14 8 external batteries 19 34 14 external batteries 35 14 external batteries 210 210 Shielded metal cabinet with an applied plastic front panel display IP215 <2G 49 77 77 115 1 mA O
DIALOG PLUS 13 . DIALOG PLUS RACK > 13.
DIALOG PLUS > 13.2 Back-up expansion modules for rack version For types and back-up times of the Dialog Plus Rack models refer to the Riello Ups’s price list. > 13.
DIALOG PLUS Dialog Plus rack 2200VA Dialog Plus rack 2200 ER VA Dialog Plus rack 3000 / 3000 ER VA 33 SPEDLPX0205REN
DIALOG PLUS Battery Box 1 - RS232 serial communication port 2 - Cooling fans 3 - IEC output sockets (max 10A) 4 - Input thermal re-settable protection 34 SPEDLPX0205REN 5 - IEC mains input plug 7 - IEC output socket 16A 6 - Battery expansion connector