UPS CONFIGURATION
The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for
individual requirements. It is possible to perform these operations using the UPStools software.
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
50 Hz
Selects the nominal output
frequency
Output frequency
Auto
60 Hz
Auto: automatic learning of the input frequency
Selects the nominal output
voltage
Output voltage
230V 220 - 240 in 1V steps
ON LINE
Selects one of the 4
different operating modes
ECO
Operating mode
ON LINE
SMART ACTIVE
STAND-BY OFF (MODE 1)
Normal
Selects the mode of use of
the bypass line
Bypass operation
Normal
Disabled with input/output synchronisation
Disabled without input/output synchronisation
Automatic UPS power-off in
battery operation mode if
the charge is lower than 5%
Power-off due to
Enabled
Disabled
minimum charge
Disabled
Maximum battery operation
time
Disabled (complete battery discharge)
Autonomy limit
Disabled
(1 - 65000) sec. in 1 sec steps
Estimated autonomy time
remaining for the battery
low warning
Battery low
3 min. (1 - 255) min. in 1 min steps
warning
Interval of time for the
automatic battery test
Disabled
Battery test
40 hours
(1 - 1000) h in 1 hour steps
Maximum charge Disabled
Selects the user overcharge
limit
Disabled
alarm threshold
(0 - 103) % in 1% steps
Selects the permitted range
for the input frequency for
switching to the bypass and
for the synchronisation of
the output
Input frequency
± 5% (±3 - ±10) % in 1% steps
tolerance range
* For configurations of the Fout = 50, 60Hz or if the sync is disabled with the input, the UPS downgrades the output power.