FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
EnergyShare
Select the auxiliary socket
operating mode
Always
connected
Always connected
Disconnection after no. seconds of battery
operation
Disconnection after no. seconds of the battery
discharge pre-alarm signal
... (see UPStools manual)
Bypass voltage
thresholds
Selects the permitted
voltage range for switching
to the bypass
Low: 180V
High: 264V
Low: 180 - 200 in 1V steps
High: 250 - 264 in 1V steps
Bypass voltage
threshold for ECO
Selects the permitted
voltage range for operation
in ECO mode
Low: 200V
High: 253V
Low: 180 - 220 in 1V steps
High: 240 - 264 in 1V steps
Intervention
sensitivity for
ECO
Selects the intervention
sensitivity during operation
in ECO mode
Normal
Low
Normal
High
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
Disabled
(1 - 255) sec. in 1 sec steps
Remote Switch
on/off feature
Select the feature
associated with the remote
control terminal board.
Pin 1-2 REPO
Pin 2-3 Remote
ON
Pin 1-2 REPO
Pin 2-3 Remote ON, Remote ON/OFF