Specifications

3255
17
GB
SETTING UP THE BURNER
After burner output has been determined, use TABLE below AS AN INITIAL GUIDE
for burner settings.
All settings in this table were obtained under the following conditions.
O
0 (zero) draft in the combustion zone;
O
Standard lab test boiler;
O
Inlet gas pressure range as in table;
O
Steady state (HOT) operating conditions.
Gas inlet
pressure range
Orifice
Manifold
gas pressure
Burner
output
Head
setting
Air gate
setting
“wc Marking “wc Btu/hr Nocth Notch
PROPANE
12.0 - 14.0
C11
3.5
170,000 0 0.9
C12 198,368 1 1.1
C13 238,170 2 1.5
C14 305,821 3 2.0
C15 334,338 4 2.1
C16 400,000 4 2.73