Installation Guide

The four RELAY LEDs indicate when the relays are activated
The STATUS LED in the center of the ACU indicates that the ACU has been configured with
firmware. It will flash green when Identify is pressed in the Control Center.
The four READER POWER LEDs indicate that the ACU has output power enabled per reader
READER LEDS
The Openpath Smart Reader’s LEDs indicate the following:
If the center dot is solid white, then the door is locked
If the outer ring is solid white, then the door is unlocked
If the center dot quickly switches between multiple colors and outer ring quickly spins once,
the reader has just received power
If all lights are off, the reader is not connected to power (check to see if the power wires are
swapped)
If the center dot is flashing red, the reader is connected to power but cannot communicate with
the ACU (check to see if the +B [blue] and -A [violet] lines are swapped)
If the center dot is solid blue, the reader is connected to power and can communicate with the
ACU, but has not been configured as an entry in the Control Center
If the center dot is solid green, and the outer ring lights up and spins, that means the reader has
been Identified via the Control Center
If the center dot is solid purple and the outer ring is solid white, the reader is possibly not
receiving enough voltage or current, potentially due to a break in wiring – try connecting the
reader directly to the ACU, bypassing any wire runs
If the center dot is solid pink and the outer ring is solid white, check that +12V IN (orange)
hasn’t been swapped with +B (blue) or -A (violet)
RESETTING THE ACU
Soft Reset: To soft reset the ACU, disconnect power from the ACU, wait 10 seconds, then reconnect
the power.
WARNING: Only hard reset the ACU if absolutely necessary and if instructed by Openpath. This
will clear all of the data off of the ACU and will require reprovisioning, which requires having a
computer or mobile phone on the same network as the ACU.
Hard Reset: To hard reset the ACU, disconnect power from the ACU, hold down the ADMIN
BUTTON, reconnect power to the ACU, wait 20 seconds while still holding the button down, then
release the button. Wait 10 minutes before re-provisioning the ACU following the PROVISIONING
THE ACU steps below.