Installation Guide
Openpath Access Control System Installation Guide
GETTING STARTED
This Installation Guide explains how to install and configure Openpath Smart Hubs (ACUs) and
Openpath Smart Readers as part of an Openpath Access Control system.
ADDITIONAL RESOURCES
● Smart Reader Data Sheet
● Smart Hub (ACU) Data Sheet
● Elevator Board Data Sheet
PRIOR TO INSTALLATION
Prior to installing Openpath hardware, it is assumed that you have performed a customer site
survey and have determined the following:
● How many entries need to be configured (e.g. doors, gates, and/or elevator floors)
● Whether you’re using legacy wiring or new wiring
● What kind of electronic entry mechanisms, Request to Exit (REX) mechanisms, and door
contact sensors will be used and their power requirements. If your locking hardware requires
24V, either use the Smart Hub ACU with included 24V power supply (OP-4ESH-24V) or use a
separate 24V supply.
○ NOTE: The Smart Hub ACU with 12V power supply (OP-4ESH-12V) supports up to 2A for
locking hardware.
● Whether you’re providing backup batteries for the ACUs. See SELECTING A BACKUP BATTERY.
● Whether you’re supporting a legacy access control panel. See WIRING TO LEGACY PANELS.
Installation
NETWORK REQUIREMENTS
An Ethernet connection with DHCP must be used to connect the ACU to the Local Area Network
(LAN). You also need to configure firewall settings to communicate with the Openpath system.
Openpath uses the following outbound ports:
● TCP port 443
● TCP port 80
● UDP port 123
Version 1.5
©
Openpath 2019
Page 3