RECOMMENDED CONFIGURATION
Openpath readers and ACUs communicate via RS-485. The following wire types are compatible,
listed in the order of preference which impacts distance.
Shielded CAT6A (recommended, additional two pairs can be used for sensors)
Shielded CAT6
Shielded RS485 w/22-24AWG (lower gauge, thicker wire is better)
Shielded CAT5
Unshielded CAT6
Unshielded CAT5
Shielded 22/6
Unshielded 22/6
Ideally, use one twisted pair for GND and VIN (power) and one twisted pair for +B and -A (data).
For shielded wiring, connect one side of the drain wire (the shield around the wires) to the GND
terminal on the ACU. Both the shield and the GND wire can share the same GND terminal. Do not
connect the other side of the shield to anything.
For standard reader installation, we recommend that you install a 1-Gang 20 CU box in order to
flush-mount the reader. Alternatively, the reader may also be surface mounted with the included
back plate.
NOTE: For elevators, all relays and readers must be connected to the same ACU. If you need more
than four access controlled floors or readers, add the Openpath Elevator Expansion Module.