Installation Sheet

Rinnai Tankless Water Heater Installaon and Operaon Manual 13
Internal (Indoor) Water Heaters
Install the water heater as far away as possible from exhaust vent hoods and dryer vents.
In coastal regions, the water heater should be installed so that it is sheltered/protected from exposure to sea
breeze. Exposure to salty spray or breeze can cause corrosion of the water heater.
Damage and repair due to corrosive compounds in the air is not covered by warranty.
Install the water heater as far away as possible from any air inlet vents. Corrosive fumes, somemes found in hair/
nail salons, spas, or other industries exposed to toxic fumes, may be released through these vents when not in
operaon. Chemicals that are corrosive in nature should not be stored or used near the water heater or vent
terminaon. This requirement applies to internal (indoor) and external (outdoor) water heaters.
External Water Heaters and Vent Terminaons
Make sure that in case of freezing weather the
water heater and its water lines are protected to
prevent freezing. Damage due to freezing is not
covered by the warranty.
When connected to a 120-volt power supply, the
water heater will not freeze when the outside air
temperature is as cold as 22°F (-30°C) for
internal (indoor) models or –4°F (-20°C) for
external (outdoor) models, when protected from
direct wind exposure. Because of the wind-chill
eect, any wind or circulaon of the air on the
water heater will reduce its ability to protect
itself from freezing.
In the event of a power failure and/or gas
interrupon at temperatures below freezing, the
water heater should manually be drained of all
water to prevent freezing damage. In addion,
drain the condensate trap, drain line and
pressure relief valve.
Loss of freeze protecon may result in water
damage from a burst heat exchanger or water
lines.
The water heater may be drained manually.
However, it is highly recommended to install the
oponal Drain Down Kit accessory that will
enable the water heater to immediately drain
upon loss of power (the condensate trap and
pressure relief valve are not aected by the Drain
Down Kit and must be manually drained).
The freeze protecon features will not prevent
the external piping and valves from freezing. It is
recommended that hot and cold water pipes be
insulated. Pipe cover enclosures may be packed
with insulaon for added freeze protecon.
Freeze Protecon
Install the water heater as far away as possible from any air inlet vents. Corrosive fumes, somemes found in hair/
nail salons, spas, or other industries exposed to toxic fumes, may be released through these vents when not in
operaon. Chemicals that are corrosive in nature should not be stored or used near the water heater or vent
terminaon. This requirement applies to internal (indoor) and external (outdoor) water heaters.
In coastal regions, the water heater should be installed so that it is sheltered/protected from exposure to sea
breeze. Exposure to salty spray or breeze can cause corrosion of the water heater.
DO NOT install the water heater in areas where combuson air might be contaminated with chemicals.
DO NOT use room air in applicaons where the indoor air is corrosive. Install the water heater as direct vent
in a sealed closet so that it is protected from the potenal of contaminated indoor air.
Cold Water
Supply Line
3/4 in. Normally Closed Solenoid Valve
1/2 in. Normally Open Solenoid Valve
Route Drain Per Local Code
Hot Water
Supply Line
Gas Supply
Vacuum Breaker *
Freeze Protecon Piping Diagram
Union
Pressure Relief Valve
Check Valve
Ball Valve
Solenoid Valve
Drain Valve
Legend
Vacuum Breaker
* Posion vacuum breaker
above water heater.