Installation Sheet
Rinnai Tankless Water Heater Installaon and Operaon Manual 17
• Internal water heaters can be installed as direct vent or non-direct vent applicaons.
• When installed as Direct Vent, refer to the “Direct Vent Approved Vent Manufacturers and Products” secon
(within the “1. Direct Vent” secon) for a complete list of approved vent manufacturers and products.
• When installed as Non-Direct Vent (Room Air), the vent must be Category IV and of a type listed by a naonal
recognized tesng agency.
• Exhaust must be directly vented to the outside. Combuson air can be provided from outside (Direct Vent) or
from room air (Non-Direct Vent).
• If using room air (non-direct vent) for combuson, ensure the required volume of indoor air is available
according to the Naonal Fuel Gas Code, ANSI Z223.1/NFPA 54.
• Avoid dips or sags in horizontal vent runs by installing supports per the vent manufacturer’s instrucons.
• Support horizontal vent runs every 4 (1.2 m) and all vercal vent runs every 6 (1.83 m) or as per vent
manufacturer’s instrucons or local code requirements.
• Venng should be as direct as possible with a minimum number of pipe ngs.
• For manufactured vent systems, vent connecons must be rmly pressed together so that the connecons form
an air ght seal. Follow the venng manufacturer’s instrucons.
• Refer to the PVC/CPVC manufacturer for appropriate ngs, solvents or joining methods.
• The vent piece connected to the water heater must be secured with 1 self-tapping screw.
• Refer to the instrucons of the vent system manufacturer for component assembly instrucons.
• If the vent system is to be enclosed, it is suggested that the design of the enclosure shall permit inspecon of the
vent system. The design of such enclosure shall be deemed acceptable by the installer or the local inspector.
• Any issues resulng from improper vent installaon will not be covered by warranty.
3.5 Vent the Water Heater
Guidelines
WARNING
DO NOT use cellular core PVC/CPVC.
DO NOT use Radel, ABS, or galvanized material to vent this appliance.
DO NOT cover non-metallic vent pipe and ngs with thermal insulaon.
DO NOT combine vent components from dierent manufacturers.
DO NOT reduce the vent diameter. Vent diameter cannot be less than 2 in. (51 mm).
DO NOT connect the venng system with an exisng vent or chimney.
DO NOT common vent with the vent pipe of any other manufacturer’s water heater or appliance.
Rinnai water heaters can only be common vented with Schedule 40 PVC/CPVC or with a Rinnai cered
common vent system.