Installation Sheet
56 Rinnai Tankless Water Heater Installaon and Operaon Manual
CONDENSATE DRAIN YES NO
If the condensate pump is installed, is it wired to deacvate the tankless water heater in the event of
failure? For more informaon, refer to the “Condensate Pump Safety Switch Wiring” secon of the manual.
Did you verify the condensate drain pipe is as short as possible and has a downward pitch toward the drain
or condensate pump?
Is all condensate drained and disposed of as per local codes?
Did you use ONLY corrosion resistant materials for the condensate drain lines?
Did you verify the condensate drain pipe along its enre length is at least the same diameter as the drain
line (1/2 in. NPT)?
Did you check to ensure the condensaon drain lines are protected from freezing?
If a oor pump is not available or the drain is above the level of the condensate drain, did you install a
condensate pump?
Have you veried the condensate drain line is not plumbed with the pressure relief valve?
Have you conrmed the condensate drain line is not connected with an air condioning evaporator coil
drain?
Have you veried an external condensate trap is not installed? (This tankless water heater has an integrated
condensate trap.)
Have you conrmed the end of the condensate drain pipe is open to atmosphere?
GAS SUPPLY YES NO
Did you verify the gas system is appropriately sized?
Did you verify the water heater is rated for the gas type supplied?
Have you performed a gas line and connecon leak test?
Did you install a manual gas control valve in the gas line to the water heater?
Is the inlet gas pressure within limits?
Did you purge the gas line of any debris before connecng the water heater?
6
7
3.14 Post-Water Heater Installaon Checklist Connued
PRESSURE RELIEF VALVE (PRV) YES NO
Does the PRV comply with the standard for Relief Valves and Automac Gas Shuto Devices for Hot Water
Supply Systems ANSI Z21.22, and/or the standard Temperature, Pressure, Temperature and Pressure Relief
Valves and Vacuum Relief Valves, CAN1-4.4?
Did you verify the PRV is rated up to 150 psi and (at least) the maximum BTU/hr of the tankless water
heater?
Is the discharge from the PRV piped to the ground or into a drain system as per local codes?
Is the discharge line from the PRV pitched downward and does it terminate 6 in. (152 mm) above the
drains?
Is the discharge end of the line plain (unthreaded) and a minimum of 3/4 in. diameter?
Is the discharge line material suitable for at least 180° F water?
Did you take measures to protect the PRV and PRV discharge line from freezing?
Have you veried the PRV is not plumbed with the condensate drain line?
Have you veried the PRV is not plugged and that reducing ngs, valves, or other restricons are not
installed in the relief line?
5