Installation Guide

10 Hydronic Air Handler Installaon and Operaon Manual
AH083CP AH084CP AH125CP AH166CP AH206CP
Appliance Type
Hydronic Air Handler
(With Internal Circulation Pump)
Installation Indoor (approved for manufactured housing and mobile homes)
Suitable for Potable Water Systems Yes
Configurations
Vertical: Upflow with bottom or side (left or right side) return
Horizontal: Upflow with bottom return
Circulation Pump Included Yes (Factory Installed)
Product Weight - lb. (kg) (approximate) 66 (30) 66 (30) 66 (30) 71 (32) 83 (38)
Cabinet Construction
Embossed cabinet in heavy gauge galvanized steel to prevent
corrosion. Cabinet lined with 5/8 in. foil faced insulation.
Nominal CFM (Cubic Feet/Minute)
800
800 1,200 1,600 2,000
Nominal Output Btu/hr at 140°F
1
30,000 40,000 50,000 60,000 60,000
Rated Voltage 120 V, 60 Hz, 1 Ph
Transformer Size and Type 40 VA, Class 2
Blower Wheel (Diameter x Width) 9x6 in. 9x6 in. 10x8 in. 10x8 in. 10x10 in.
Blower Motor Type 3-Speed PSC
Blower Motor Hot Water Coil Rows 3 4 3
Blower Motor Coil Material Copper Coil, UV Resistant Pan
Blower Motor Horsepower (HP) 1/3 1/3 1/2 3/4 3/4
Blower Full Load Amps (FLA) 5.3 5.3 7.1 7.5 10.5
Water Connection 3/4 in. Sweat
Pump Voltage 120 V
Pump Amps 1.4 Amps
Control Board
Factory Installed
Freeze protection activates at 40°F and deactivates at 70°F
Thermostat connections
60-second time delay for blower activation
Pump timer circulates water for one minute every six hours to
prevent stagnation of water in the system
Boiler activation dry contact
24V AC isolation valve control
Certifications ETL Listed
Rinnai products are continually being updated and improved; therefore, specifications are subject to
change without prior notice.
1
Reference tables in sections 3.8.4 and 3.8.5 for specific BTU output.