Installation Guide

Hydronic Air Handler Installaon and Operaon Manual 47
Entering Water
Temperature
Flow
Rate
Blower
Speed
Seng
BTU Output
(Air Handler Models)
Maximum Equivalent
Pipe Length (.)
1
AH083P AH084P AH125P AH166P AH206P
i060C/
i090C
i120C
120°F
3
Low 20,000 22,000 30,000 37,000 36,000
40 40
Medium 21,000 24,000 32,000 38,000 37,000
High 23,000 26,000 33,000 39,000 37,000
140°F
Low 25,000 31,000 42,000 53,000 51,000
Medium 30,000 34,000 45,000 54,000 52,000
High 32,000 37,000 46,000 56,000 53,000
160°F
Low 33,000 40,000 55,000 68,000 66,000
Medium 39,000 44,000 58,000 70,000 68,000
High 42,000 48,000 60,000 72,000 69,000
120°F
4
Low 21,000 23,000 32,000 41,000 40,000
10 10
Medium 23,000 26,000 34,000 43,000 41,000
High 24,000 28,000 36,000 44,000 42,000
140°F
Low 29,000 32,000 46,000 58,000 57,000
Medium 32,000 36,000 48,000 60,000 58,000
High 35,000 39,000 51,000 62,000 60,000
160°F
Low 38,000 42,000 59,000 75,000 74,000
Medium 41,000 47,000 62,000 78,000 76,000
High 45,000 51,000 66,000 80,000 77,000
Models:
i060C
i090C
i120C
1
Refer to section “8.3.1 Equivalent Feet of Pipe Per Fittingfor more information on determining the maximum
equivalent pipe length.
IMPORTANT
If more than 40 equivalent feet of plumbing is needed with the I-Series Boiler, Rinnai recommends the use
of hydraulic separation with an external circulation pump. Hydraulic separation uses primary/secondary
piping to separate the boiler from the heating system. Hydraulic separator examples include a low loss
header (field-supplied), closely spaced tee (field-supplied), or the Primary-Secondary Heating Kit offered
by Rinnai (part # 807000212).