Installation Manual
14 Hydronic Air Handler Installaon and Operaon Manual
Air Handler
Model
Entering Water
Temperature
Blower Speed (Btu/hr)
Low Medium High
AH083P
120°F 21,000 23,000 25,000
140°F* 29,000 32,000* 35,000
160°F 38,000 42,000 45,000
AH084P
120°F 23,000 25,000 27,000
140°F* 32,000 35,000* 38,000
160°F 41,000 46,000 50,000
AH125P
120°F 32,000 33,000 35,000
140°F* 44,000 47,000* 49,000
160°F 57,000 60,000 63,000
AH166P
120°F 41,000 42,000 44,000
140°F* 58,000 60,000 62,000*
160°F 75,000 78,000 80,000
AH206P
120°F 41,000 42,000 43,000
140°F* 58,000 60,000 61,000*
160°F 75,000 77,000 78,000
Air Handler
Model
Entering Water
Temperature
Blower Speed (Btu/hr)
Low Medium High
AH083P
120°F 21,000 23,000 25,000
140°F* 29,000 32,000* 35,000
160°F 38,000 41,000 45,000
AH084P
120°F 23,000 25,000 27,000
140°F* 32,000 35,000* 39,000
160°F 41,000 46,000 50,000
AH125P
120°F 32,000 34,000 35,000
140°F* 45,000 47,000* 50,000
160°F 58,000 61,000 64,000
AH166P
120°F 41,000 43,000 44,000
140°F* 58,000 60,000 62,000*
160°F 75,000 78,000 80,000
AH206P
120°F 41,000 42,000 43,000
140°F* 58,000 60,000 61,000*
160°F 76,000 77,000 79,000
•
IMPORTANT
• All capacities are based on 70°F entering air temperature.
• For entering air temperatures other than 70°F, use the following capacity correction factors:
(72°F x .982), (68°F x 1.02), (66°F x 1.04)
• Glycol correction factors: (10% X .98), (20% X .95), (30% X .92), (40% X .88)
• Refer to the “Approved Cleaners, Inhibitors and Antifreezes” section (in the Appendix of the “I-Series
Condensing Combi Boiler Installation and Operation Manual”) for a complete list of approved glycols.
* Bold text
is default
setting
•