Installation Manual
Hydronic Air Handler Installaon and Operaon Manual   21 
•  Install ductwork in accordance with NFPA 
90B and any local codes. 
•  Install the conditioned air plenum, ducts 
and air filters (not provided) in accordance 
with NFPA 90B Standard for the 
installation of Warm Air Heating and Air-
Conditioning Systems (latest edition). 
•  Isolation connectors (if utilized) must be 
nonflammable.  
•  Duct connections for the air handler with 
hot water heat must allow room for water 
piping connections to be made in the 
upflow configuration. 
•  A return air duct system is recommended. 
If the unit is installed in a confined space or 
closet, a return connection must be run, full 
size, to a location outside the closet. 
•  The air handler is provided with flanges for 
the connection of the plenum and ducts. 
•  Air filters must be listed as Class 2 furnace 
air filters. 
•  Supply and return ductwork must be 
adequately sized to meet the system’s air 
requirements and static pressure 
capabilities. Ductwork should be insulated 
with a minimum of 1 in. (25 mm) thick 
insulation with a vapor barrier in 
conditioned areas or 2 in. (51 mm) 
minimum in unconditioned areas. 
•  Supply plenum should be the same size as 
the flanged opening provided around the 
blower outlet and should extend ideally at 
least 3 ft. (1 m) from the air handler before 
turning or branching off plenum into duct 
runs. The plenum forms an extension of 
the blower housing and minimizes air 
expansion losses from the blower. 
•  All wiring must conform to local and national 
electrical codes. Improper wiring or 
installation may damage thermostat. 
•  Air Conditioner Model: The Standard Model 
A/C thermostat may be wired with or without 
connecting a common wire between the 
indoor equipment and the thermostat. 
However, it is recommended to use a 
common wire whenever possible to prevent 
power stealing by the thermostat. 
•  Heat Pump Model: The standard model 
heat pump thermostat is not "power 
stealing" and must have both ‘R’ and ‘C’ 
wires connected to operate properly. The 
thermostat should have an indicator for 
when auxiliary heat is in use. 
•  The thermostat should NOT be mounted: 
−  Close to a window, on an outside wall, 
or next to a door leading to the outside  
−  Exposed to direct light and heat from a 
lamp, sun, fireplace, or other heat-
radiating objects which may cause a 
false reading 
−  Close to or in direct airflow from supply 
registers and return-air grilles  
−  In areas with poor air circulation, such 
as behind a door or in an alcove 
Before installing or servicing the air handler, 
turn off power to unit. There may be more 
than one disconnect switch. Electrical shock 
can cause personal injury or death. 
 WARNING 










