3
Air Handler
Model
Entering
Water Temp
Blower Speed (Btu/hr)
Low Medium High
AH083CP
120°F 21,000 23,000 24,000
140°F* 29,000 31,000* 34,000
160°F 37,000 40,000 43,000
AH084CP
120°F 22,000 25,000 27,000
140°F* 31,000 35,000* 38,000
160°F 40,000 44,000 47,000
AH125CP
120°F 31,000 33,000 34,000
140°F* 43,000 45,000* 47,000
160°F 55,000 58,000 61,000
AH166CP
120°F 40,000 41,000 42,000
140°F* 55,000 57,000 58,000*
160°F 70,000 73,000 75,000
AH206CP
120°F 40,000 41,000 41,000
140°F* 55,000 56,000 57,000*
160°F 70,000 71,000 72,000
Air Handler
Model
Entering
Water Temp
Blower Speed (Btu/hr)
Low Medium High
AH083CP
120°F 21,000 23,000 25,000
140°F* 29,000 32,000* 34,000
160°F 38,000 41,000 45,000
AH084CP
120°F 23,000 26,000 28,000
140°F* 32,000 35,000* 39,000
160°F 41,000 45,000 49,000
AH125CP
120°F 32,000 34,000 35,000
140°F* 44,000 46,000* 49,000
160°F 57,000 60,000 63,000
AH166CP
120°F 42,000 43,000 44,000
140°F* 57,000 59,000 61,000*
160°F 74,000 76,000 79,000
AH206CP
120°F 41,000 42,000 43,000
140°F* 56,000 57,000 58,000*
160°F 73,000 74,000 76,000
* Bold text is default seng.
Air Handler
Model
Entering
Water Temp
Blower Speed (Btu/hr)
Low Medium High
AH083P
120°F 21,000 23,000 25,000
140°F* 29,000 32,000* 35,000
160°F 38,000 42,000 45,000
AH084P
120°F 23,000 25,000 27,000
140°F* 32,000 35,000* 38,000
160°F 41,000 46,000 50,000
AH125P
120°F 32,000 33,000 35,000
140°F* 44,000 47,000* 49,000
160°F 57,000 60,000 63,000
AH166P
120°F 41,000 42,000 44,000
140°F* 58,000 60,000 62,000*
160°F 75,000 78,000 80,000
AH206P
120°F 41,000 42,000 43,000
140°F* 58,000 60,000 61,000*
160°F 75,000 77,000 78,000
Air Handler
Model
Entering
Water Temp
Blower Speed (Btu/hr)
Low Medium High
AH083P
120°F 21,000 23,000 25,000
140°F* 29,000 32,000* 35,000
160°F 38,000 41,000 45,000
AH084P
120°F 23,000 25,000 27,000
140°F* 32,000 35,000* 39,000
160°F 41,000 46,000 50,000
AH125P
120°F 32,000 34,000 35,000
140°F* 45,000 47,000* 50,000
160°F 58,000 61,000 64,000
AH166P
120°F 41,000 43,000 44,000
140°F* 58,000 60,000 62,000*
160°F 75,000 78,000 80,000
AH206P
120°F 41,000 42,000 43,000
140°F* 58,000 60,000 61,000*
160°F 76,000 77,000 79,000
• All capacies are based on 70°F entering air temperature.
• For entering air temperatures other than 70°F, use the following capacity correcon factors: (72°F x .982), (68°F x 1.02),
(66°F x 1.04)
• Glycol correcon factors: (10% X .98), (20% X .95), (30% X .92), (40% X .88)
• Refer to the “Approved Cleaners, Inhibitors and Anfreezes” secon (in the Appendix of the “I-Series Condensing Combi Boiler
Installaon and Operaon Manual”) for a complete list of approved glycols.
* Bold text is default seng.
* Bold text is default seng.
* Bold text is default seng.
Tankless water
heaters must
have a minimum
input rate of
160,000 Btu/hr.