Installation Manual
40         Canadian Air Handler Installation and Operation 
Menu  Parameter  Description  Min  Max  Default 
Configuration  Language  Switch between English and French  -  -  English 
Cooling/HP 
AC/HP Tons  Set the cooling/heat pump capacity (Tons)  0  10  0 
CFM/TON  Airflow adjustment per ton of cooling (CFM)  300  500  400 
Dehum ON State  Set the active state of the DH signal  LOW  HIGH  HIGH 
Dehum Ratio 
(1)
  Dehumidification cooling fan ratio  50%  100%  85% 
AC Y1 Ratio 
(1)
  Fan ratio for 1st cooling stage  50%  90%  70% 
Fan 
Cont Fan Ratio 
(1)
  Continuous Fan Ratio  15%  100%  50% 
Heat Fan Ratio 
(1)
  Fan ratio in heating mode (W/W2)  35%  100%  75% 
Fan W1 Ratio 
(2)
  Fan ratio for 1st heating stage  45%  100%  50% 
Heat Off Ratio 
(1)
  Fan ratio during off delay  0%  100%  40% 
Pump 
Recirculation   Time between recirculation (hours)  OFF  48  24 
W1 Ratio  Pump ratio for 1st heating stage  1%  100%  13% 
Purge Cycle 
Time during the pump will operate after a call 
for heating 
1 sec 
240 
sec 
1 sec 
Purge Ratio 
(5) 
Pump activation frequency during purge cycle  1%  100%  6% 
Delays 
AC/HP On  Fan delay when heat pump starts  5  120  5 
AC/HP Off  Fan delay when heat pump stops  5  240  90 
Heat On  Fan delay when engine starts  5  120  5 
Heat Off  Fan delay when boiler stops  0  240  120 
(1) 
Ratio in percentage of max airflow (Y2) 
(2) 
Ratio in percentage of max airflow of 1600 CFM 
(3)
 Ratio in percentage
of max hydronic heating airflow (W/W2) 
(4) 
Ratio in percentage of heating airflow (W1 or W2) 
(5) 
Reduce the value if the water heater activates during the purge cycle 
TROUBLESHOOTING: 
Insufficient or no heat: 
•  Check filter, replace if dirty 
•  Verify the hydronic coil is not clogged.  
•  Verify there no air trapped in the heating loop. Purge the loop if air is present. 
•  Verify Rinnai Engine operation and water temperature. Clean inlet water filter on Rinnai engine. 
•  Verify there are no restrictions in the heating loop. Verify all valves are fully open and functional.  
The pump does not run: 
•  Verify 120V power is present to the pump 
•  Hard water may cause the pump to seize. Recirculation mode will prevent pump seizing. 
The pump is noisy at start-up: 
•  Purge the hot water loop of air. 
Heating during the fan on mode: 
•  Verify the check valve in the heating circuit is present and is not stuck.  