Installation Guide

Rinnai Tankless Water Heater Installation and Operation Manual 21
Table 6. Clearances
The water heater is not exposed to corrosive compounds in the air.
The water heater location complies with the required clearances.
The planned intake air and exhaust termination locations meet the required clearances.
The water supply does not contain chemicals or exceed total hardness that will damage
the heat exchanger.
A standard 3 prong 120 VAC, 60 Hz properly grounded wall outlet or other 120 VAC, 60
Hz source is available.
The installation must conform with local codes or, in the absence of local codes, with the
National Electric Code (NEC), National Fuel Gas Code, ANSI Z221.3/NFPA 54, and/or
CSA B149.1, Natural Gas and Propane Installation Code.
Use this checklist to ensure you have selected the correct location for the water heater.
Figure 7: Clearances
Location Clearance to Combustibles and Non-Combustibles
Top 2 in. (51 mm) (0 in. from vent components)
Bottom/Ground 12 in. (305 mm)
Front 0 in. (Clearance for servicing is 24 in. / 610 mm in front of water heater)
Back 0 in.
Sides (Left and Right) 2 in. (51 mm) (Add 0.25 in. / 6.35 mm for recess box)
Vent 0 in.
TOP
BOTTOM
SIDE
FRONT
CAUTION
If clearances are not met, damage to the property and water heater
may occur.