Installation Guide

Rinnai Tankless Water Heater Installation and Operation Manual 91
COMBINATION SPACE HEATING/POTABLE WATER SYSTEM
(For Use In Commonwealth of Massachuses)
When the system requires water for space heating at temperatures higher than required for other uses, a means such
as a mixing valve shall be installed to temperature the water for those uses in order to reduce scald hazard potential.
Air handler
Use Only in Commonwealth of Massachusetts
Electronically controlled
pump timer. Activates every
6 hours for 60 seconds.
Wire to product approved
pump. (or built
- in pump)
Hot Water
Supply and
Return to
Heating Coil
Tempered water to plumbing fixtures. Must
meet temperature requirements of 248 CMR
Automatic Tempering Device Must be installed
below the top of the water heater as per
manufacturer's recommendations.
Check Valve
Cold Water
Supply
Shut Off Valve
Check Valve with 1/8in. Hole
Drilled in Clapper Optional
Expansion
Tank
Product
Approved
Water Heater
100'-00" maximum distance from water
heater to fan coil and back. (Developed
length) not including coil in heating unit.
Piping loop between
water heater and fan coil
shall be in compliance
with 248 CMR.
NSF-61 Product
Approved Pump
Check Valve
Gas supply
Min. 2' developed
length Type L copper
from water heater
Air handler
Combination Space
Heating/Potable
Water System
All water piping should be
insulated in accordance with
780 CMR (Massachusetts
Energy Code)
Hot water coil
System installed with reverse
acting aquastat to shutoff
fan. Suggested but not
required by 248 CMR.
Figure 102