Install Instructions

Installation & Servicing Instructions Rinnai E-Series
152
Code Description Solution
Erreur unité de commande Véri ez la stabilité 120V. Si la tension dévie plus qu'entre +10% et -15%,
l’alimentation électrique doit être stabilisée.
Vériez le câble ruban entre l’unité de commande et l’afcheur; si
nécessaire remplacez-le
L’erreur persiste après reset Erreur du logiciel de l’unité de commande, remplacez l’unité de commande.
l’unité de commande va automatiquement charger le programme dans la
nouvelle unité de commande.
Control unit error Moisture on the PCB. Check if there is water leaking on or in the boiler.
Stop leak and replace MCBA controller
Control unit error
1 Anticipation resistance wire not
present
When a power stealing room stat device is placed the connection terminal
needs to be provided with the special anticipation resistance wire.
2 Software error control unit. Software error control unit. Replace the control unit. Remove the E-Prom from
the defective control unit and place it onto the new control unit .The controller
will automatically load the program into the new control unit.
High limit stat open Supply temperature too high. Caused by
- presence of air
- possible polluted impeller of the circulation boiler pump
- polluted internal lter
Check de-aerator. Replace when necessary the automatic de-aerator and
restart boiler for de-aerating programm (17min.)
Check water ow over system. Clean when necessary the pump and or
lter. Flush complete system
Check adjustment of balancing valves
Control unit error Software error control unit. Replace the control unit. Remove the E-Prom from
the defective control unit and place it onto the new control unit .The controller
will automatically load the program into the new control unit.
- T1 ow sensor ground
connection
- T1 ow sensor failure
- controller failure
Check the data in Error mode. Boiler data during error:
1 Error = 14
2 Operational status = 00
3 Flow temp. = -22
4 Return temp. = xx*
5 kW burner = 00**
6 % pomp = xx*
* = variable values
**= x3415=BTU/hr
A temperature of - 36 is displayed at position 3.
Check the wiring and/or measure the resistance of the ow sensor. The
resistance should be approx. 12 kOhm at 77°F.
(See table in Appendix B)
If necessary, replace the ow sensor
- check for resistance on 16 and 17 if using a 3rd part DHW control
- if resistance is present on 16 and 17 with 3rd party control contacts on
control are not fully open
Signal maximum ow water
temperature exceeded (T
1
>
212°F).
Check actual ow temperature. suddenly increase caused by completely
hydraulic shut off of the boiler ( lter, pump, thermostat valve, service
valve)
Check ow sensor NTC1. measure the resistance value (see Appendix B)
Exchange defective part if necessary. Change control unit when error
persists.