Install Instructions

Installation & Servicing Instructions Rinnai E-Series
33
6.7.4 Direct vent closet and alcove installation
For closet and alcove installation, CPVC material, instead of PVC, must be used
in a closet/alcove structure. Failure to follow this warning could result in re,
personal injury, or death.
Rinnai strongly suggests the use of PPs venting for all closet and alcove
installations. For non direct vent room air applications see sections 6.7.5 and
6.7.8.
12" (300 mm)
minimum
12" (300 mm)
minimum
12" (300 mm)
minimum
INTAKE
EXHAUST
12" (300 mm)
minimum
12" (300 mm)
minimum
Terminal positions PVC figure 16
!
WARNING
15”
386mm
6”
148mm
11”
268mm
Closed door
1”
25,4mm
10”
254mm
1”(25mm) minimum clearance
around vent pipes
2”
50mm
2”
50mm
1”(25mm) minimum clearance
around hot water pipes
8”
200mm
8”
200mm
Closet installation gure 17
10”
254mm
15”
386mm
1”(25mm) minimum clearance
around vent pipes
6”
148mm
11”
268mm
Open front
6”
152mm
2”
50mm
8”
200mm
8”
200mm
2”
50mm
1”(25mm) minimum clearance
around hot water pipes
Alcove installation gure 18