15 Blocks and Errors
15.1 Error indication (short reference)
A detected error is indicated on the display by means of blocking or error messages. A
distinction should be made between these two messages due to the fact that blocking
can be of a temporary nature, however, error messages are xed lockings. The control
will try its utmost to prevent locking and will temporarily switch off the unit by blocking
it. The following is a list of some messages.
Blocks with a number in the last 2 positions.
Block 01:
External safety contact cut off
Block 05:
Outdoor sensor not connected
Block 60:
Incorrect parameter setting of the minimum or maximum power.
Block 67:
A T has been detected between ow and return sensor whereas the burner is not in operation.
After the T has disappeared the block will clear.
Block 85:
The control has not detected a water ow. The venting cycle is started.
If during this cycle water ow is detected, the venting cycle is ended and the burner is released.
Error with a number in the last two positions.
Error 00: Poor ame-forming
Error 02: no ame-forming
Error 04: adjustment or error for voltage interruption
Error 05: adjustment
Error 12: high limit stat
Error 18: maximum ow temperature exceeded
Error 19: maximum return temperature exceeded
Error 28: number of revolutions not reported back from fan
Error 69: no or incorrect display
FUSE: 24V fuse defective
The following pages describes more detailed follow up instructions for solving
blockings, errors and practical circumstances. These instructions are only for
licensed professional.