Submittal Sheet

E110CR Condensing Boiler
E110CR-SP-2 8/2017
© 2017 Rinnai Corporation
SPECIFICATIONS
Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior
notice. Local, state, provincial and federal codes must be adhered to prior to installation.
Standard Features
Factory Installed Boiler/System Modulating Pump
Onboard Outdoor Reset Control System with Sensor Standard
Priority Domestic Hot Water (DHW) Standard
Built-in DHW Plate Heat Exchanger
Modulating Ceramic Premix Burner
4.2:1 Turndown Ratio
Spark Ignition
Exceeds SCAQMD 1146.2 Low NO
x
Requirements
Stainless Steel Water Tube Condensing Heat Exchanger
Direct Vent Sealed Combustion
Twin Pipe Venting Adapters Included
Approved for Room and Closet Installations (Zero Clearance to
Combustibles)
Optional Accessories
RS100 Single Zone Controller
Flue Gas Temperature Sensor
Room Air Filter
Flow Switch Conversion Kit
Low Loss Header Plumbing Kit
Low Loss Header Side Mount Kit
General Specifications
Water Content 1.3 Gal / 4.8 L
Max. Supply Boiler
Temperature
176 °F / 80 °C
Max Operating Pressure 45 PSI / 310 kPa
Relief Valve Rating 375 MBH / 110 kWh
Relief Valve Pressure Rating 30 PSI / 207 kPa
Unit Weight 92 lbs / 42 kg
Min Inlet Gas Pressure NG 4.0" WC / 10.0 mbar
Max Inlet Gas Pressure NG 10.5" WC / 26.2 mbar
Min Inlet Gas Pressure LP 8.00" WC / 19.9 mbar
Max Inlet Gas Pressure LP 13.5” WC / 33.6 mbar
Electrical Voltage Mains 120 V / 60 Hz
Electrical Voltage Controls 24 V
Power Consumption Max Load 145 W
Power Consumption Standby
Load
14 W
Recommended Circuit Breaker
Rating
15 A
Sound Level 49 dB
Performance Specifications
Fuel Types NG and LP
Input (Heating) 110 MBH / 32.2 kWh
Heating Capacity 101 MBH / 29.6 kWh
Input (DHW) 130 MBH / 38.1 kWh
Minimum Input
NG: 26 MBH / 7.6 kWh
LP: 59 MBH / 17.4 kWh
Turndown Ratio 4.2:1 / 1.9:1 TDR
System Pump Model UPER 20-78
Max Head Pressure at Flow
Rate
13.8 ft at 5.0 GPM
4.2 m at 18.9 LPM
AFUE 95.5%
DHW Flow Rate 75°F ΔT 3.2 GPM / 12.1 LPM
DHW Minimum Activation 0.5 GPM / 2.0 LPM
Flow Restrictor Color Green
Max Equivalent Exhaust Vent
Length
100 ft / 30.5 m
Max Equivalent Combustion Air
Vent Length
100 ft / 30.5 m
Approved Venting Materials
Polypropylene, Stainless
Steel, PVC, CPVC

Summary of content (2 pages)