Specifications
Installation & Servicing Instructions E-Range
10
The maximum absorbed current consumption of the external circulation pump may be
230 W (1 Amp). The extra external pump must be selected according to the installation
resistance and the required flow.
As standard the boiler is provided with a water filter in the return pipe of the boiler. With
this, possible contamination of the central heating water is prevented from ending up in
the boiler. The boiler is also provided with an internal safety valve set at 3 bar. This is
connected to the waste discharge together with the condensation discharge.
pump index lines graph 1
If all, or a large part of the radiators are provided with thermostatic radiator valves it is
advisable to use an automatic bypass in order to prevent flow problems in the installation.
The boiler is designed to be used on a sealed system only.
Use only potable water for filling the heating system.
When the water hardness of the filling water exceeds > 200ppm and the
volume of the installation > 20L/kW the water has to be treated until below
the maximum value of 200ppm.
The pH value of the installation water must be between 5 and 8.5.
Additives in the installation water are only permitted in consultation with the
country distributor.
Q(m³/h)
E32S
UP 20-60
H(m)