User Guide

Installation & Servicing Instructions Rinnai E-Series
19
To protect the entire heating system we recommend installing a dirt particle
trap in the return circuit. When the boiler is installed to an existing heating
system this trap is required. Use of a Y strainer is not permitted as substitute
for a dirt trap.
- Position H3 (fi gure 7) is a garden hose thread boiler drain, that can be used to
drain the boiler or add water treatment additives to the system, such as inhibitors
or glycol.
- For information on locating the expansion tank and system ll, please see the
Rinnai Boiler Applications Manual.
The boiler is designed to be used on pressurized heating systems only (closed
loop).
If the boiler is to be installed in a system that utilizes zone pumps and not zone valves
a low loss header plumbing kit should also be installed (part number: 804000061).
If the pressure drop in the loop/system is greater than the available head pressure
from the boiler pump a low loss header plumbing kit should be used (part number:
804000061).
NOTICE
i
NOTICE
i
pump index lines graph 1
0
2
4
6
8
10
12
14
024681012
Q [gallons/min]
PSI
UPER 20-58 (max.) UPER 20-78 (max.) Pressure drop E110SPressure drop E60S/E85S
32.3
27.7
23.0
18.5
13.8
9.2
4.6
0
Feet of head
E60SR/E85SR
E110SR
SXPSW\SH SHUPLVVLEOHLQVWDOODWLRQUHVLVWDQFH
JDOORQVPLQ JDOORQVK 36,N3D)RRWRIKHDG
6\VWHP (651(653 83(5   
(651(653 83(5   
(651(653 83(5   
%RLOHUW\SH ZDWHUIORZUDWH
pump capacity table 5