Rinnai ENERGYSAVER® Direct Vent Wall Furnace Installation Fundamentals
Rinnai ENERGYSAVER® Direct Vent Wall Furnace Installation Fundamentals The following course is approved for NATE continuing education hours (CEH’s). This course will earn the following CEH’s: Warm Air Heating-Gas-Installer – 2 hours Warm Air Heating-Gas-Service – 2 hours If you require credit for NATE, please notify the instructor at this time.
Rinnai Service and Support (800-621-9419) Rinnai America’s phone support structure consists of the following departments: • CRC – Consumer Response Center – Fielding general calls, consumer questions, etc. • Available in office from 8 a.m. to 8 p.m. EST, Monday - Friday • Parts and Warranty Department – Fielding parts orders and warranty issues • Available in office from 8 a.m. to 5 p.m.
Product Model Numbers and Specifications NEW MODELS PREVIOUS MODELS CFM* MAX POWER* DECIBELS* INPUT BTU RANGE* AFUE (Efficiency)* EX08C ES08, RHFE 201 FA 55.5-82.0 41-42 W 27-36dB 3,000-8,000 NG/LP NG-82% LP 83% EX11C ES11, RHFE 263 FAII 69.3-102.5 44-47 W 31-38dB 5,500-11,000 NG 5,700-11,000 LP NG-81% LP-82% EX17C ES17, RHFE 431 FAIII EX17, RHFE 431 WTA 111.3-137.8 40-46 W 33-38dB 8,200-16,700 NG/LP NG-81% LP-82% EX22C ES22, RHFE 556 FAIII EX22, RHFE 556 WTA 111.3-162.
Features and Benefits • When sized correctly, the ENERGYSAVER® Furnace can be used as a whole house/primary heat source.
Features and Benefits • The unit’s standby power consumption is less than 1 watt. • Seven-stage Intelligent Modulating Gas Valve and blower control. • Warm air discharge at floor level. o Directional louvers to optimize direction of air flow. • Ultra-quiet operation-Decibel range of 27-47 is comparable to a normal conversation. • Gas type is field convertible. • Restart Functions allow automatic restart after ignition, combustion, or power failures. • Small 3” diameter concentric vent.
Safety Features • Self Diagnostic Circuitry-Should the ENERGYSAVER® detect an unsafe operating condition, the unit will shut down and a fault code will display indicating the specific issue. o If the code is due to an ignition or combustion failure, the unit will attempt to relight automatically. • Function/Child Lock • Cool to the touch Cabinets.
Safety Features • Overheat protection- Multiple temperature sensors monitor the appliance’s temperature. Shut down occurs if an unsafe operational temperature is detected. • Combustion and convection fan validation-should either of these fans fail to maintain the proper speed (likely due to a restriction), the PCB will not allow the unit to operate. • Electronic ignition-no standing pilot. • Power failure protection-Should the ENERGYSAVER lose power, the gas supply will automatically close.
ENERGYSAVER® Sizing To ensure the ENERGYSAVER operates as designed, an industry standard Btu heat loss calculation must be performed on the area to be heated.
ENERGYSAVER®—Whole House Furnaces Key concepts The ENERGYSAVER has the ability to heat an entire structure from a central room. Here’s how: • 2nd law of thermodynamics – Heat seeks cold • Once the main room approaches the set point temperature, the heat begins to move to other rooms—seeking cold. • The variable gas valve and blower control modulate to ensure heat reaches the remainder of the structure without overheating the main area.
ENERGYSAVER®—Whole House Furnaces Key concepts • Variable speed technology – Modulating gas and air based on the heat loss at that moment • With on/off single stage operation, gas usage can be high due to alternating periods between maximum flame and no flame at all • The Energysaver’s modulating technology has the ability to replace only the heat escaping the structure by continuously operating at heating levels based on the demand at that moment On / Off Single Stage Heating Appliance Continuous-Run Mo
ENERGYSAVER® Direct Vent Furnaces Operation Sequence 1. Combustion fan purges heat chamber, PCB verifies fan rotation Concentric Termination Convection Fan 2. Ignition spark begins 3. When sensing electrode detects spark, gas valve assembly opens 4. Ignition occurs and heat exchanger warms 5. Spark stops as flame rod & PCB verify flame 6. When heat exchanger is warm enough, convection room blower circulates warm air into the structure. Flame Rod Combustion Fan Heat Exchanger 7.
Control Panel Review (C-Series models) EX08C, 11C, 17C, 22C MODELS Temperature Control and DisplayDisplay will enter a power saving dimmer mode during normal operation Restricted Filter Indicator Operation Lamp Green = standby Solid red = when flame is present Flashing red = fault code is present Child Safety Lock Economy Feature Timer 1 and 2 Note: While off, pressing Timer 1 and 2 together will change the display from F° to C° Override Temporarily bypasses timers Timer and Clock Setup Setback Feat
Control Panel Review (C-Series models) Description Key The following pages will cover each topic in detail 1. 2. 3. 4. 5. Child Safety Lock Economy Feature 1 2 Timer 1 and 2 Note: While off, pressing Timer 1 and 2 together will change the display from Fahrenheit to Celsius Override Temporarily bypasses timers Temperature Control and Display- 9 3 5 4 6 7 8 10 EX08C, 11C, 17C, 22C MODELS 3 5 9 7 Display will enter a power saving dimmer mode during normal operation 6. 7. 8.
Control Panel Review (all other current models) ES38 MODELS Production before 7/2011 Temperature Control and Display Room temp lamp stays on Room temp displays only when adjusted Economy Feature Function Lock Pressing both arrows will engage The below table shows the temperature range of all models Fahrenheit Celsius L (approx. 55) L (approx. 13) 60 62 64 66 68 70 72 74 76 78 80 H (approx. 95) 16 17 18 19 20 21 22 23 24 25 26 H (approx.
Economy Function Economy Mode is designed to save gas usage over time. • The Economy Function is based on the theory that the human body cannot detect small temperature changes over an extended period of time. • 30 minutes after the set point temperature is achieved, the unit will reduce the temperature by 2°F. After 30 additional minutes, the unit will reduce the temperature an additional 2°F. • The maximum temperature reduction will not exceed 4°F.
Clock, Timer, and Setback Functions (C-Series) C-Series ENERGYSAVERS® have two primary methods of operation: • Exclusively as a thermostatically controlled furnace • When left to operate on a continuous-run basis using feedback from its thermostat, the ENERGYSAVER will achieve an optimum balance between comfort and efficiency.
Clock, Timer, and Setback Functions (C-Series) • If needed, the Override button can be selected to temporarily turn on or off the timers to allow manual operation. • If the unit is operating during a Timer’s event, pressing Override will turn the unit off until the next Timer’s event. • If the unit is off between Timer events, pressing Override will turn it on. It will continue to run until the end of the next Timer’s event and return to Timer operation.
Clock, Timer, and Setback Functions (C-Series) Setback allows a minimum temperature to be pre-set and maintained between timer events or while the unit is turned off. • This feature’s primary function is to slightly reduce the temperature (and gas usage) during extended periods of nonuse or inactivity—such as sleeping or when the home is empty. • NOTE: When this feature is used as a setback function for energy savings, it is not advisable to reduce setback more than 4-6°F from the regular set point.
Restart Features All ES, EX, and C-Series models will attempt restart after a power failure or flame failure to ensure heating is not interrupted for extended periods of time. • If there is a power failure while the appliance is operating, the unit will attempt to restart automatically when the power is restored. • The timers will retain their settings after a power outage. • After an outage, the clock will retain the time at that moment until power resumes.
Restart Features • Should a high gust of wind, gas outage, etc. occur that affects the flame characteristic, the unit will automatically shut down, purge the combustion chamber, and re-ignite. • If the unit cannot ignite or maintain flame for 15 seconds after ignition, code 11 will flash and the unit will try to ignite again in one hour. • This code will not be stored in the fault code history.
Fault Codes • A fault code will flash on the unit when a fault occurs. The unit will stop operating. • Operation intervention is required for all codes EXCEPT a code 11.
Warranty and Maintenance • Warranty Rinnai ENERGYSAVER® Furnace Warranty Heat Exchanger Coverage Parts Reasonable Labor 10 years 5 years 2 years Refer to each model’s installation and owner manual for full warranty details • Maintenance and Service • The appliance should be inspected at least annually by a qualified service technician—see the installation manual for full details. • The exterior can be cleaned with a damp, warm cloth.
High Altitude and Gas Conversion • All units are approved up to 10,200 feet. • The Installation manual and the conversion manual supplied with each unit has instructions for high altitude settings. • High altitude conversion does not require additional or replacement parts—only a simple manifold gas pressure adjustment. • Only a dual port manometer will be required to complete this adjustment. • All EnergySaver® furnaces can be field converted from NG to LP or LP to NG.
Maximum Temperature Limit • All ENERGYSAVER® models now have the ability to set a maximum temperature limit directly from the control panel. This procedure is NOT in the manuals to allow property owners and managers to control this setting as needed. • This is beneficial to landlords and property management to conserve energy and reduce unnecessary gas consumption.
Installation Overview This overview is not meant as a substitute for the installation and owner’s manual. Every furnace is shipped with a manual that should be followed completely. The following is a supplemental presentation and is intended as a tool for the first time installer. QUALIFIED INSTALLING AGENCY The installation must conform to local codes, in the absence of local codes, the installation must conform with American National Standard (National Fuel Gas Code) known as NFPA 54 and ANSI Z223.
Installation Guidelines The following guidelines are from the installation / owner’s manual. Before beginning the installation process, please review the following: •A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a standard is not applicable, the standard for Manufactured Home Installations, ANSI/NCSBCS A225.
Installation Guidelines The following guidelines are from the installation / owner’s manual. Before beginning the installation process, please review the following: • This appliance discharges a large volume of warm air next to the floor. Any particles in the air such as cigarette smoke could cause discoloration in carpet. The warm air flow could discolor nylon carpets containing dyes or vinyl surfaces.
Recommended Tools Needed for Installation • • • • • • • • • • • • • Cordless / Electric drill 3 inch hole saw 5/8 inch X 18 inch pilot drill bit 1/8 inch drill bit (not shown) No. 2 Phillips bit No.
View of Properly Installed Unit 30
Furnace Packaging and All Hardware *Included with furnace: Ensure correct gas type is on package! • Installation and owner’s manual • Wall termination that will fit wall thickness of 4.5”-9.
Furnace Packaging and Hardware Inspect packaging to ensure all parts and installation materials are removed before discarding. Top of box contains screw hardware, back-spacers, vent termination, etc.
Furnace Packaging and all Hardware HARDWARE PACKET Machine screws for attaching exhaust pipe to termination sleeve Back spacer mounting brackets Exhaust pipe stoppers and clamps Longer tie wrap for securing intake hose to back frame Screws for attaching exhaust sleeve (3) and top back spacer (2) to wall Sheet metal screws for attaching back spacers to furnace Sheet metal screws for attaching air intake clamps (not used on all models) Shorter tie wrap for securing air intake hose to termination CAUTION U
Installing On Combustible Flooring • When the furnace is installed directly on carpeting or other combustible material (excluding wood flooring), it must be installed on a metal or wood panel extending the full width and depth of the heater. • The furnace may be installed on combustible wood flooring. 1. The packing board used for shipping can also be used to place under the unit if needed when installing on carpet. 3. Cut board to fit full width of unit. 2.
Identifying the Installation Location FURNACE LOCATION Furnace must be installed where the proper clearances from combustibles can be maintained. Also ensure installation location is not in an area of excessive cold or warm air conduction.
Identifying the Installation Location VENT LOCATION Consider the following requirements when locating the outside vent termination: • 12” clearance from grade or anticipated snow level (ANSI Z223.1) • 9” clearance from a door or window that may be opened (ANSI Z223.1) • 3 feet clearance above a forced air inlet located within 10 feet (ANSI Z223.
Interior Wall Preparation TEMPLATE PLACEMENT Included with each furnace is a wall template to simplify mounting and vent hole location—2010 and newer models have the template printed on the cardboard packaging. 1. Cut the template out of the box. 2. Ensure bottom of template is cut correctly. 3. Temporarily tape the template to the wall at floor level. 4. Ensure template does not slip.
Interior Wall Preparation SCORING THE WALL 1. Ensure vent hole will NOT compromise any structure support (stud), electrical, plumbing, HVAC system, etc. Score two mounting screw holes (⅛” bit) CAUTION Practice good safety habits when using power equipment 2. Score the template anywhere in the shaded arc for the pilot bit. 3. Also score the two screw holes for the mounting wall bracket with a ⅛” bit. 4.
Interior Wall Preparation INSTALLING THE MOUNTING BRACKET Using the two previous scored screw holes, mount the rear mounting bracket to the wall.
Interior Wall Preparation DRILLING THE VENT HOLE 1. Interior: Using a 3” inch hole saw, drill the vent hole guided by the previously drilled pilot hole. NOTE: Drill holes level or sloped downward 2°to the outside. Vent termination must have outward pitch to ensure condensation drains to the outside. 2. Exterior: Continue drilling hole guided by the previously drilled pilot hole.
Initial Gas Line Preparation ATTACHING THE GAS CONNECTION (Part 1) 1. Prepare the drip leg for furnace connection. NOTE: Do not attach the right side back spacer yet to allow enough space for tightening these fittings. 2. Attach the drip leg to the furnace. Use two wrenches to prevent damage to the furnace. 3. If using appliance flex gas line (recommended), attach flair adaptor to the drip leg. NOTE: The connection of the flexible gas line will be covered in a following procedure.
Furnace Preparation INSTALLING THE LEFT AND RIGHT BACK SPACERS The left and right back spacers are installed with a tab and slot at the top and middle and single screws at the bottom of the panels. Ensure two locking tabs align correctly ROOM AIR THERMISTOR NOTE: The room air thermistor comes with approximately 14” of wire. It can be moved higher if needed if there is an excessive amount of cold air conduction present. This should be a last resort—ideally, the cold air conduction should be eliminated.
Furnace Preparation INSTALLING THE AIR INTAKE HOSE CLIP Mount the hose clip at the bottom of the furnace as shown below. Models prior to 2010 use a clip in this location-see manual for details.
Vent Termination VENT TERMINAL PREPARATION • The flue manifold (vent) must exhaust to the outside. Do not exhaust into other rooms. • The flue is not designed to be positioned under floors or below the furnace. • Clearance to combustibles for the vent sleeve and flanges is zero inches. • This appliance can only be used with one of the five types of Rinnai vent kits. These kits and their dimensions are listed below and in each owner’s/installation manual.
Vent Termination FLUE MANIFOLD DISASSEMBLY • The flue manifold consists of 3 parts: • Inside connection • Sleeve • Outside terminal 1. Disassemble the flue manifold by first pulling out the inside connection. NOTE: Make sure the black gasket is always on the interconnector piece as shown. 2. To remove the outer terminal pull and release the two internal stainless steel ties and then pull out the outer terminal.
Vent Termination ADJUSTING THE SLEEVE LENGTH Do not extend vent beyond the red line! 1. Measure the wall thickness through the previously drilled hole. The end of the sleeve should protrude 3/16” – 3/8” (510mm) from the outside wall. The sleeve is threaded for adjustment. Adjust the sleeve length to wall thickness PLUS 3/16” – 3/8”(5-10mm). NOTE: Do not extend beyond the red line on the sleeve. CAUTION Practice good safety habits when using sharp tools! 2.
Vent Termination ATTACHING THE SLEEVE 1. Slide the sleeve through the interior side of hole. Ensure label “Top” is installed at the top of hole. 2. Ensure the sleeve extends 3/16” to 3/8” (510 mm) NOTE: The flange is offset 2°to allow condensate to drain outside 3. Attach the sleeve to the inside wall using 3 screws. If needed, use sheet rock anchors to secure to wall.
Vent Termination INSTALLING THE OUTER VENT TERMINAL 1. From the outside, insert the terminal into the sleeve with the marking “TOP” at the top. The left hand side locking tie should be marked “LEFT.” 2. For weather board walls (lap siding), add the second seal next to the terminal seal to compensate for siding angle. Terminal Seal Additional angled seal for lap siding 3. On the inside, pull hard on the left and right hand ties. Clip the ties over the notches inside the sleeve.
Vent Termination INSTALLING THE INSIDE CONNECTION ASSEMBLY 1. Push the assemble into the terminal tube with the label “top” matching the location on the sleeve. Ensure that the seal is in place on the inner tube. 2. Attach the inside connection with 3 screws. NOTE: The inner connection can still be turned to install the screws.
Vent Termination OUTSIDE VIEW OF CORRECTLY INSTALLED TERMINATION 50
Final Gas Line Preparation ATTACHING THE GAS CONNECTION (Part 2) Tip: Using a flexible appliance gas line will enable the furnace to be slid into place with minimal effort. 2. Attach the included shut off 3. NOTE: Many models will valve and field supplied allow the gas valve to be flexible gas line to the wall positioned behind the back supply and furnace. Leak test spacer but still accessible all connections. by the consumer. IMPORTANT: Ensure all code and gas line sizing requirements are followed.
Sliding the Furnace into Place SLIDING THE FURNACE INTO PLACE 1. If necessary, the unit can be leveled using the adjustable legs under the front right and left hand sides. 2. Slide the furnace into place. Ensure furnace is level and aligned to vent termination, back spacer mounting bracket, and gas line (if necessary).
Connecting the Vent Flue CONNECTING THE VENT FLUE The following components can be connected by reaching behind the appliance as it is positioned against the wall NOTE: NEVER bend the exhaust pipe that exits the furnace! 1. Slide the stainless steel exhaust tube until it is fully inserted into the manifold. 2. When sliding the tube, ensure it does not extend beyond the red line. NOTE: Never bend the exhaust pipe that exits the furnace. 3. Connect the flue outlet to the manifold.
Connecting the Vent Flue CONNECTING THE VENT FLUE (continued) The following components can be connected by reaching behind the appliance as it is positioned against the wall Insulation sleeve 3. Fit the locking clamp over the connection between the sliding tube and manifold. Engage the hook and rotate it until it snaps against the body of the clamp. 4. Slide the insulation sleeve up to the flue manifold. Slip the securing clips over the sleeve as shown.
Connecting the Air Intake CONNECTING THE AIR INTAKE The following components can be connected by reaching behind the appliance as it is positioned against the wall: 1. Connect the air intake hose to the side of the termination. NOTE: NEVER cut the gray air intake hose. It is sized to length for a standard termination. 2. Using the zip tie provided, fasten the air intake to the termination.
Installing the Top Back Spacer The following components can be connected by reaching behind the appliance as it is positioned against the wall. 1. Install the bracket on the rear of the top spacer with 2 decorative sheet metal screws. 2. Place top back spacer on the back of furnace, clipping the spacer bracket into the wall bracket.
Installing the Top Back Spacer (continued) 1. Insert screws for top spacer on right and left side of back spacers. 2. Tighten two sheet metals screws on top back spacer.
Prepare for Operation 1. If needed remove the toe kick plate to fill the humidifier tray. 2. Fill the humidifier tray according to the installation manual. Replace toe kick plate. 1. To direct air flow, if needed, the front louvers can be adjusted after removing louver plate (5 screws). 2. Install the filter. 3. Open all gas valves. 4. Turn unit on and set temperature. 5 screws secure louver plate Vertical louvers can be gently turned to direct air flow 5. Educate consumer on use and care.
ES38 Vent and Gas Connection Differences Shipped with each ES38 is a vent adaptor that reduces the 50 mm diameter exhaust to 30 mm for connection to vent termination. NOTE: If using extension sets, this reducer must be connected to the VENT TERMINATION ONLY! Do not use the smaller extension sets with this reducer installed at the furnace. The ES38 will not operate correctly. Included with the ES38 is male to female “street” elbow to attach to the unit before a union or flex line.
Extended Venting And High Altitude Installation Procedures 60
Vent Extension Installation Requirements The following is an overview of guidelines and installation of Rinnai Direct Vent Furnace vent extensions. This is not a substitute for any current installation / owner’s manual or vent instructions. • The 08 series can not use vent extensions. • See each model’s owner’s / installation manual for permissible vent lengths. • The vent termination must ALWAYS be horizontal.
Vent Extension Installation Requirements The following is an overview of guidelines and installation of Rinnai Direct Vent Furnace vent extensions. This is not a substitute for any current installation / owner’s manual or vent instructions • The exhaust elbow assembly attached on the back of the unit must remain as a 90° elbow. Never bend or straighten this component. • Do not shorten the intake air hose attached to unit from factory. This hose can never be cut or altered in length.
Specific Venting Changes • The table below illustrates each model’s permissible vent length and kit part numbers ES08/EX08C ES11/EX11C ES17/EX17(C) ES22/EX22(C) ES38 Total extended vent limit 0 13 feet 13 feet 13 feet Total vertical limit 0 8 feet (unless greater than 2000’ altitude then only 5’ for the ES11 10 feet 13 feet Use kit FOT-155 Use kit FOT-219 Use kit FOT-102 Use kit FOT-156 Use kit FOT-220 Use kit FOT-103 Use kit FOT-157 Use kit FOT-221 Use kit FOT-114 Use kit FOT-158 Us
PCB Adjustments for extended venting or high altitude MODELS: EX08C, EX17C, EX22C, ES38 These models do not require an adjustment for vent length—only for high altitude With power off, remove front cover and press the test button on the PCB.
PCB Adjustments for extended venting or high altitude MODEL: EX11C With power off, remove front cover and press the test button on the PCB.
Selecting the Correct Vent Extension Kit EXAMPLES OF EXTENSION SETS • The following examples are for ES11 /EX11C Models. • Other models will vary. • Instructions and all hardware are included.
Vent Extension Installation Guidelines PROPER VENTING INSTALLTION GUIDELINES Example: Using 2 sets of extensions and 1 standard bent elbow Example: Using the 80” extension set VERTICAL RISE OF EXTENSION FROM TOP OF THE FURNACE TO THE TERMINATION OR ELBOW CANNOT EXCEED 10 FEET ON THE 17 OR 22 MODELS! (Other models may vary, see Owner’s / Installation Manual) Use the pipe stoppers, connectors, clamps, and screws according to each extension CAUTION set and model’s installation instructions to ensure no lea
Vent Extension Installation Guidelines PROPER VENTING INSTALLTION GUIDELINES INCORRECT! INCORRECT! • Only two elbows are allowed! • Venting cannot be turned down! CAUTION • Never arrange elbows where condensation can collect in the venting! CORRECT! • Slope venting where condensation is allowed to drain! Use the pipe stoppers, connectors, clamps, and screws according to each extension set and model’s installation instructions to ensure no leakage of exhaust gases! 68
Alternate Vent Termination Options ALTERNATIVE TERMINATION CONNECTION Flexibility for venting terminations is engineered into every Rinnai unit. Note below where the exhaust alignment position can be changed by moving the stainless steel plug for two additional positions depending on the application. Likewise note the two positions for intake air flexibility. 1. Remove the plug from the back of the termination 2. Reposition the plug to the bottom of the termination where labeled “exhaust” 3.
Vent Extension Installation Guidelines PREPARING FOR EXTENSION INSTALLATION 1. Located on the top back spacer are two sets of two punch outs (one on the left and one on the right). Remove the two that the extension will travel thru. Discard the excess sheet metal. 2. If the top back spacer is already secured to the furnace, temporarily remove it to allow fastening of the extension components to the furnace air intake and exhaust. 3.
Vent Extension Installation Guidelines INSTALLING THE EXHAUST EXTENSION 1. The exhaust is connected between the bent pipe at the rear of the furnace and the exhaust port on the flue Telescopic manifold. extension 2. Connect exhaust pipes with other straight pipes or bends (including the furnace exhaust) by fitting the male end into the female end. Pipe Stopper A Pipe Stopper B Female end 3. If needed, extend the telescopic portion of the extension to the desired length.
Vent Extension Installation Guidelines CONNECTING THE AIR INTAKE EXTENSION 1. The air intake extension is connected between the air connection at the rear of the heater and the air intake port on the flue manifold. 3. Remove the air intake elbow from the furnace intake hose (reverse threaded). Move this elbow to the end of the air intake extension. 2. Cut the air intake extension to the desired length.
Vent Extension Installation Guidelines MOUNTING COMPONENTS 1. Both the exhaust and air intake extensions are supported by clamps which are attached to the wall. A wall fixture can be used to offset the clamp from the wall. A one inch clearance from combustibles should always be maintained from the exhaust. The clamps provided with the extension kit ensure this clearance is maintained from the wall and the air intake. 2.
Decorative Covers For Vent Extension Kits 74
Vent Extension Decorative Cover EXAMPLES OF VENT COVERS Basic Installation Vent Cover with Elbow Vent Cover and Termination Cover 75
Vent Extension Decorative Cover EXAMPLES OF VENT COVERS Basement Installation rough in stage Basement Installation finishing stage Basement Installation painted vent cover Painted without priming 76
Vent Extension Decorative Cover INSTALLATION OVERVIEW • • • • • The simple design provides an easy and attractive way to cover vent extensions The mounting bracket is installed to the wall behind the extension venting The cover is mounted to the bracket from the sides The cover is paintable aluminum and can be custom cut. All covers are sold as kits.
Vent Extension Decorative Covers – New ES Series MODEL ES38 TYPE OF VENT COVER Flue Manifold Cover ES11, EX11C, ES/EX17(C), ES/EX22(C) Use kit FOT-132 Manifold Kit A Use kit FOT-140 Manifold Kit B Vent Cover Use kit FOT-133 Straight Cover Kit A Use kit FOT-141 Straight Cover Kit B Vent Cover Elbow Use kit FOT-134 Elbow Cover Kit A Use kit FOT-142 Elbow Cover Kit B DIAGRAM WITH DIMENSIONS NOTES: • ES08/EX08 models cannot use extended venting • Each kit comes with all required mounting hardware
This completes the direct vent installation course. Please contact technical support with any questions or issues.