• Should a high gust of wind, gas outage, etc. occur that affects the flame
characteristic, the unit will automatically shut down, purge the combustion
chamber, and re-ignite.
• If the unit cannot ignite or maintain flame for 15 seconds after ignition,
code 11 will flash and the unit will try to ignite again in one hour.
• This code will not be stored in the fault code history.
• If at some point after 15 seconds of established flame the flame fails,
the unit will immediately attempt to relight with no code flashing.
• If the unit cannot relight after this flame failure, code 11 will flash and
the unit will try to ignite again in one hour.
• If the unit continually or intermittently fails to ignite, a qualified service
technician may be needed to determine the cause.
• Each manual has a section named “Restart Function” that explains this
procedure.
• Flame failure fault codes (code 12’s) are no longer needed due to this
enhancement.