Louvers and Grills
When sizing the permanent opening consideraon
must be taken for the design of the louvers or grills to
maintain the required free area required for all gas
ulizing equipment in the space. If the free area of the
louver or grill design is not available, assume wood
louvers will have 25% free area and metal louvers or
grills will have 75% free area. Under no circumstance
should the louver, grill or screen have openings
smaller than 1/4”.
Example:
Wood: 10 in x 12 in x 0.25 = 30 in
2
Metal: 10 in x 12 in x 0.75 = 90 in
2
Locaon
To maintain proper circulaon of combuson air two
permanent openings (one upper, one lower) must be
posioned in conned spaces. The upper shall be
within 12” of the top of the conned space and the
lower opening shall be within 12” of the boom of the
conned space. Openings must be posioned as to
never be obstructed.
Using Outdoor Air For Combuson
Outdoor air can be provided to a conned space
through two permanent openings, one commencing
within 12 in. (300mm) of the top and one commencing
within 12” (300mm) of the boom, of the conned
space. The openings shall communicate to the outside
by one of two ways.
Vent terminaon per ANSI Z223.1/NFPA 54. For
clearances not specied in ANSI Z223.1/NFPA 54,
clearances are in accordance with local installaon
codes and the requirements of the gas supplier.
(Be sure to also maintain 12” above grade or
ancipated snow level)
Combuson Air Requirements
Exhaust