I Series Solo Installation Manual
100
Rinnai I-Series Condensing Boiler Solo Manual
Flame Failure
Boiler has ame failure.
Check that the gas is turned on at the
boiler, gas meter, and/or propane
cylinder.
If the unit is installed in a propane
system, ensure that gas is in the tank.
Ensure the venng is installed in
accordance to this manual.
Ensure the ame rod wire is connected.
Ensure the gas type and inlet gas
pressure are correct.
Bleed all air from the gas lines.
Check the ground wire to the PC Board.
Check ame rod voltage to ground
during ignion.
Heat Exchanger Overheat
Overheat switch is tripped.
Measure the resistance of the Overheat
Switch.*
Check the heat exchanger surface for
hot spots which may indicate blockage
due to scale buildup.
Ensure the boiler pump is not locked up.
Ensure that all of the valves in the CH
circuit are open.
Ensure the boiler and CH circuit does not
have a freezing condion.
The surface of the heat exchanger may
turn to a black color as stainless steel is
tempered even in normal condions.
This does not indicate an abnormal
condion.
Check for damage on the exhaust, seal,
and venng.
Venturi Control
Venturi operaon error.
Ensure the venturi motor is operang
correctly.*
Replace the gas valve assembly.
Venturi Blockage
Check the venturi and silencer for
blockage.
Before reseng this error, check if the
condensate drain is block and if the
venng is connected properly.
* See “Electrical Diagnoscs” on Technical Data
Sheet located on inside front cover of boiler.
Indirect Tank Temperature
• Indirect tank runs for more than six hours
without cycling o.
• Ensure the tank size is adequate.
• Check the thermistor locaon.
• Ensure the system is plumbed properly.
• Check the supply temperature for tank is
higher than tank seng temperature
(Parameter 30).
• Check sensor wiring for damage.
• Measure resistance of sensor.*
• Replace sensor if necessary.
Electrical Grounding
Secondary circuit ground fault.
Check all electrical components for
electrical short.
Condensate Pump (Accessory)
Boiler will operate for 60 seconds.
Conrm wire connecons and harnesses
are good.
Ensure the condensate reservoir is
empty and condensate pump is
operaonal.
Freeze Protecon Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Supply Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
Indirect Tank Thermistor
Ensure DIP switch 4 is set to the
appropriate seng.
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
Exhaust Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.