I Series Solo Installation Manual

119
Rinnai I-Series Condensing Boiler Solo Manual
1. Locate the PC Board (lower le side of unit) (Figure 3).
2. Locate the red buon on the PC Board (Figure 3).
3. Press and hold the red buon for ve seconds (Figure 3).
Figure 3
4. Press the Mode buon on the controller.
5. Scroll to parameter and press the
Select buon.
6. Press the (Up) or (Down) arrows to select
the appropriate gas type.
Select for Natural Gas (NG)
Select for Propane (LP)
Then, press the Select buon.
7. Parameter sengs are complete. To enter normal operaon mode, press the Mode buon.
Press and Hold
Red Buon
for Five Seconds
NATURAL GAS
PROPANE
PC Board