I Series Solo Installation Manual
120
Rinnai I-Series Condensing Boiler Solo Manual
SATISFACTORY
Front View
Blue Flame
Flame
Rod
UNSATISFACTORY
Front View
Yellow or Green Flame
Flame
Rod
Figure 4
3. Reinstall the boiler front panel using the four screws to secure it.
1. Check the normal operang sequence:
a. When you press the ON/OFF buon, the LED display will illuminate, the combuson fan
will begin to run if water is owing, and the spark will ignite the main burner.
b. This boiler has an automac ignion system. When the main burner has lit, the “In Use”
lamp will glow red and the spark will stop.
2. Visual inspecon of ame:
a. Check that the burner ames are operang normally. The ame can be seen through the
circular window above the burner. When operang normally, the burner ame should
burn evenly over the enre surface. The ame should be clear, blue, and stable. A yellow
ame is abnormal and maintenance is required (Figure 4).