I Series Solo Installation Manual
51
Rinnai I-Series Condensing Boiler Solo Manual
Listed below are common components in a
Central Heang system. Refer to the diagram
on the next page.
Expansion Tank — A properly sized
expansion tank charged to 2 PSI (14 kPa)
below the cold system pressure is required
to limit pressure changes in the heang
system. When replacing an expansion tank,
consult the expansion tank manufacturer
for sizing.
Air Separator — An air separator is needed
on the central heang supply side of the
system to remove any air that may be
present in the piping.
Pressure/Temperature Gauge — The
current pressure and temperature will
alternately be displayed on the boiler
control panel. A port for an external gauge
is present in the Primary-Secondary
Heang Kit accessory oered by Rinnai.
Plumb the heang supply line to the
heang supply connecon on the
boom of the boiler.
Pressure Relief Valve (PRV) — A PRV
located directly on the supply side of
the boiler is required. The PRV must be
3/4 in. with at least 30 PSI (207 kPa)
and a maximum of 45 PSI (310 kPa). A
30 PSI (207 kPa) PRV is supplied with
the boiler. A port for the central
heang PRV is present in the Primary-
Secondary Heang Kit accessory
oered by Rinnai.
Oxygen Eliminaon — The boiler may
only be installed in a pressurized closed
-loop heang system, free of air and
other impuries. If using oxygen
permeable tubing in the central heang
system, a plate heat exchanger is
necessary to isolate the tubing and
boiler.
Low Water Cut O (LWCO) — This
boiler has a factory-installed pressure
sensor type LWCO. The boiler's internal
LWCO is not serviceable or adjustable.
Check your local codes to determine if
a LWCO is required and if this device
conforms to the local code. If a LWCO is
required to be installed, the probe
must be located higher than the
minimum safe water level. When a
LWCO is installed, it must be wired
back to the appropriate terminal on the
boiler PC Board.
Water Fill Valve — Maintains proper
water pressure in the central heang
circuit.
Back Flow Preventer — Use a back
ow preventer in the lling circuit to
the appliance as required by local code.
Dirt Trap — Protects the boiler from
debris in the plumbing system.
Heang Supply Connecon