I Series Solo Installation Manual

68
Rinnai I-Series Condensing Boiler Solo Manual
Devices such as the room thermostat and outdoor temperature sensor are connected to the boiler
PC Board.
Conrm that the electricity is supplied from a 120 VAC, 60 Hz power source and is in a
properly grounded circuit.
Conrm that an extension cord or adapter plug has NOT been used with the boiler.
Conrm connecon terminals are connected correctly.
PC Board
Rinnai recommends the use of spade connectors or similar
components for wiring to the screw terminals.
Ensure that the insulaon of the wire is not exposed to
contact any other components besides the terminal.
If exposed wiring contacts to any other exposed wiring or
metal components, an electrical short may occur and cause
damage to the PCB or other connected components.
Use proper size of screwdriver for prevenng the screw on
the terminal from breaking.
Do not use an electric or torque screwdriver for wiring on
the PC Board.
Wiring should pass through the grommets provided at the
boom of the boiler.
Use the proper diameter and size of wiring.
CAUTION
Item Connecon Item Note
Boiler Pump 120 VAC, Max 2.0 A
External Pump Connecon 2/
Indirect Pump
120 VAC, Max 2.0 A
External Pump Connecon 1 120 VAC, Max 2.0 A
T/T 1 Connecon
T/T 2 Connecon/Indirect
Tank Thermostat Connecon
LWCO (High Limit or Other
Safety Switch)
Included Jumper
from Factory
Outdoor Temperature Sensor
Indirect Tank Thermistor
24V AC for External Output Max 0.7 A