I Series Solo Installation Manual

71
Rinnai I-Series Condensing Boiler Solo Manual
DO NOT bypass the deaeraon program during commissioning or if any part of the system has
been opened or disconnected. Failure to properly deaerate the boiler and system may result in
damage to the boiler, which is not covered by the boiler warranty.
To iniate or end the deaeraon process, press and hold the top, le black buon on the PC Board
(shown below).
DIP Switches
Deaeraon is an eecve method of purging air from the boiler aer the system has been lled or
serviced. While the boiler is running the deaeraon process, the Maintenance Required icon
(see right image) appears on the controller display.
Do not bypass deaeraon during commissioning or if the system pressure has dropped
below 13 PSI (90 kPa). If there is any chance that air has entered the system, deaeraon is crical
to prevent damage to the boiler.
PC Board
WARNING