Boost mode allows the boiler to override the target temperature determined by the outdoor reset
control, and will boost the boiler target temperature to the seng of Parameter 01 aer a
connuous run me or an interval as selected in Parameter 02. The boost funcon is acve unl the
call for heat is sased or the boiler cycles o.
Boost mode works when the outdoor sensor detects higher outdoor temperatures than expected.
For example: In the case of selecng curve 1 on parameter number and 30 minutes on parameter
number , outdoor temperature is 51°F, and supply temperature is 140°F. When the boiler
connues operang with ring for 30 minutes, the target supply temperature will rise toward 180°F.
This control connues unl shut down.
80
100
120
140
160
180
200
0 10 20 30 40 50 60 70 80
0°F
(-18°C)
20°F
(-7°C)
40°F
(4°C)
80°F
(27°C)
Outdoor Temperature
Supply Temperature
Example
180°F
(82°C)
140°F
(60°C)
51°F
(11°C)
Curve 1
The maximum outdoor temperature parameter seng enables the boiler to shut down when the
outdoor temperature is higher than 77°F (25°C). This mode can prevent the boiler from operang
under warm condions unexpectedly.
Maximum outdoor temperature is selected by seng parameter number to “77°F (25°C)” or
“No Maximum” (see secon “12.4 Parameter Sengs” for more informaon).
200°F (93°C)
180°F (82°C)
160°F (71°C)
140°F (60°C)
120°F (49°C)
100°F (38°C)
0°F
(-18°C)
20°F
(-7°C)
40°F
(4°C)
80°F
(27°C)