Installation Manual

10 Rinnai I-Series Condensing Boiler Solo Manual
1
Maximum gas supply pressure must not exceed the value specied by the manufacturer.
Rinnai products are connually being updated and improved; therefore, specicaons are subject
to change without prior noce.
Model i060S i090S i120S i150S
Dimensions - w, h, d 18.5 in. x 26.4 in. x 11.45 in. (471 mm x 671mm x 290 mm)
Weight 59.2 lb (27 kg) 62.0 lb (28 kg)
Appliance Type Wall-Mounted, Gas-Fired Solo boiler
Installaon Type Indoor
Ignion System Direct Electronic Ignion
Heat Exchanger Surface Area
9.3 sq  10.9 sq 
Gas Consumpon
(Btu/h)
Minimum 15,000
Maximum 60,000 90,000 120,000 150,000
CH (Minimum - Maximum) 86°F - 180°F (30°C - 82°C)
Temperature
Seng
Indirect Tank
(DHW)
120°F - 150°F (50°C - 65°C)
Water Content
0.75 gal 0.88 gal
Water Pressure
CH
Minimum: 13 PSI (90 kPa) Maximum: 45 PSI (310 kPa)
Recommended: 17-26 PSI (117-180 kPa)
Pressure Relief
Valve (included
with system)
30 PSI (207 kPa)
Sound Level 37 dB(A) 41 dB(A) 40 dB(A) 42 dB(A)
Electrical Data
Normal 36 W 50 W 50 W 50 W
Standby 4 W
Max Current
6 Amps
Fuse
10 Amps x 2
Gas
Supply Pressure
1
Natural Gas
3.5 in. - 10.5 in. W.C. (0.87 - 2.61 kPa)
Propane
8.0 in. - 13.5 in. W.C. (1.99 - 3.36 kPa)
Electric Connecons
AC 120 Volts, 60 Hz
Cercaons
ANSI Z21.13, CSA 4.9, ASME
Canada CRN 2089.9CL