Installation Manual

100 Rinnai I-Series Condensing Boiler Solo Manual
120
Flame Failure
Boiler has ame failure.
Check that the gas is turned on at the
boiler, gas meter, and/or propane
cylinder.
If the unit is installed in a propane
system, ensure that gas is in the tank.
Ensure the venng is installed in
accordance to this manual.
Ensure the ame rod wire is connected.
Ensure the gas type and inlet gas
pressure are correct.
Bleed all air from the gas lines.
Check the ground wire to the PC Board.
Check ame rod voltage to ground
during ignion.
140
Heat Exchanger Overheat
Overheat switch is tripped.
Measure the resistance of the Overheat
Switch.*
Check the heat exchanger surface for
hot spots which may indicate blockage
due to scale buildup.
Ensure the boiler pump is not locked up.
Ensure that all of the valves in the CH
circuit are open.
Ensure the boiler and CH circuit does not
have a freezing condion.
The surface of the heat exchanger may
turn to a black color as stainless steel is
tempered even in normal condions.
This does not indicate an abnormal
condion.
Check for damage on the exhaust, seal,
and venng.
Ensure the parameter A0 corresponds to
the gas type the unit is installed in.
Ensure the gas orice is the proper
orice for the gas type in use.
Ensure deaeraon has been performed.
150 Venturi Control
Venturi operaon error.
Ensure the venturi motor is operang
correctly.*
Replace the gas valve assembly.
170
Venturi Blockage
Check the venturi and silencer for
blockage.
Before reseng this error, check if the
condensate drain is block and if the
venng is connected properly.
* See Electrical Diagnoscson Technical Data
Sheet located on inside front cover of boiler.
181
Indirect Tank Temperature
Indirect tank runs for more than six hours
without cycling o.
Ensure the tank size is adequate.
Check the thermistor locaon.
Ensure the system is plumbed properly.
Check the supply temperature for tank is
higher than tank seng temperature
(Parameter 30).
Check sensor wiring for damage.
Measure resistance of sensor.*
Replace sensor if necessary.
190
Electrical Grounding
Secondary circuit ground fault.
Check all electrical components for
electrical short.
250
Condensate Pump (Accessory)
Boiler will operate for 60 seconds.
Conrm wire connecons and harnesses
are good.
Ensure the condensate reservoir is
empty and condensate pump is
operaonal.
310
Freeze Protecon Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
353
Supply Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.
371
Indirect Tank Thermistor
Ensure DIP switch 4 is set to the
appropriate seng.
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
380
Exhaust Thermistor
Check sensor wiring for damage.
Clean the surface of the sensor.
Measure the resistance of the sensor.
Check the return thermistor.
Replace if necessary.