Installation Manual

Rinnai I-Series Condensing Boiler Solo Manual 101
540
High Exhaust Temperature
Check the exhaust thermistor wiring for
damage.
Clean the surface of the thermistor.
Measure the resistance of the exhaust
thermistor.*
If the sensor has been replaced and the
error sll appears, check the return
thermistor.
Check the exhaust duct, seal, and
venng for damage.
610
Combuson Fan
Check the motor wire harness for loose
or damaged connecons.
Measure resistance and voltage of
motor wire harness.*
Ensure the combuson fan spins freely.
700
PC Board
PC Board circuit error.
Replace PC Board.
710
Solenoid Valve Circuit
Ensure Dip switch 5 on the PC Board is in
the OFF posion (default).
Ensure the gas control wire is not loose
or damaged.
Replace the PC Board.
720
Flame Rod
Check the ame rod and wire for
damage.
Ensure the ame rod and wire are not
wet.
If there is no issue with the ame rod or
wiring, replace the PC Board.
890 Freeze Issue
The boiler checks the heat exchanger
temperature at the me of operaon.
If the temperature is too low, an error
will occur.
Check if there is freezing in the boiler or
CH system.
* See Electrical Diagnoscson Technical Data
Sheet located on inside front cover of boiler.
363
Return Thermistor
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
393 Outdoor Thermistor
Ensure that DIP switch 1 is set to the
appropriate posion.
Check sensor wiring for damage.
Measure the resistance of the sensor.
Replace if necessary.
400 Pressure Sensor
Check sensor wiring for damage.
Measure the voltage of the sensor.
Replace if necessary.
430
High/Low Water Pressure
If the water pressure is too low, add
water into the system unl at least 13
PSI is observed.
Ensure there are no leaking
components in the CH system.
If the pressure is too high, adjust the
pressure to a maximum of 30 PSI.
Ensure the pressure relief valve and
water ll are working correctly.
Ensure deaeraon has been
performed.
443
Low Water Cut-O (LWCO)
Ensure the LWCO device is working
correctly.
Ensure the LWCO jumper is connected
properly when LWCO is not in use.
Ensure the output is 24 VAC on the
PCB. If it is not, check the transformer
harness and output of the transformer.
520
Solenoid Valve Circuit
Check the ame rod and wire for
damage.
Close the gas shut o valve installed
near the boiler.
Ensure the ame rod and wire are not
wet.
Check the output from the PC Board to
the solenoid gas valve.
If the output from the PC Board is
abnormal, replace the PC Board.
If the output from the PC Board is
normal, replace the gas control.