Installation Manual
102 Rinnai I-Series Condensing Boiler Solo Manual
999
PC Board Mismatch
• This code occurs when the PC Board and
the internal logic do not match.
• Check if the soware versions of the
board and operaon board do not match.
FFF
Maintenance Indicator
• This code is a placeholder in diagnosc
code history indicang a service provider
performed maintenance or service.
• Enter this code aer performing service
by pressing and holding the Up buon,
then press and hold the Down buon,
and then press the Indirect Tank buon
simultaneously. FFF will appear on the
display.
No
Code
Boiler does not start heang with a heang
demand present
• Supply temperature or return
temperature inside the boiler may be too
hot.
• Ensure the pump operates properly.
No
Code
Boiler does not start heang the indirect
tank, although the indirect tank is calling for
heat
• Aer the tank priority me (Parameter
34) passes, the boiler will be in heang
priority for 60 minutes.
No
Code
The boiler does not operate with the CH
seng buon
• If DIP switch 2 is OFF, CH operaon will
operate via the room thermostat.
* See “Electrical Diagnoscs” on Technical
Data Sheet located on inside front cover of
boiler.
No
Code
Supply temperature is dierent
from the seng temperature on
the controller
• During outdoor sensor control,
the supply temperature will
vary dependent on the outdoor
temperature.
• During simultaneous operaon
of an Indirect Tank and CH, the
supply temperature for CH is
based on Indirect Tank control.
No
Code
CH capacity is insucient
• Ensure the parameters are
properly set for the installaon.
• During simultaneous operaon
of an Indirect Tank and CH, ow
volume to heang can be
reduced.
No
Code
Pump or fan even with no demand
• The boiler may start or operate
the pump for freeze protecon
operaon.
• The pump may intermiently
operate to prevent it from
becoming stuck.
Up and Down
Press the
Indirect Tank
buon
E;FFF