Installation Manual

Rinnai I-Series Condensing Boiler Solo Manual 107
AFTER SERVICING: VISUAL INSPECTION OF FLAME
Verify proper operaon aer servicing. The burner must ame evenly over the enre surface when
operang correctly. The ame must burn with a clear, blue, stable ame. See the parts breakdown
of the burner for the locaon of the view ports. The ame paern should be as shown in the
images below:
SATISFACTORY
FRONT VIEW
BLUE FLAME
FLAME ROD
YELLOW OR GREEN FLAME
FLAME ROD
UNSATISFACTORY
FRONT VIEW
Intake Filter
Inspecon:
To maintain opmum performance, periodically inspect the air lter.
If the air lter appears to have lint and/or dust build up, follow the
cleaning procedure described below.
If the air lter appears damaged, contact a trained and qualied
professional for a replacement air lter assembly.
Cleaning:
Clean the Air Filter: With mild dish soap and a so bristle brush, scrub the
lter area of the air lter door. With clean water, rinse the soap o the
lter.
Dry the Air Filter: With a lint free towel, dry the air lter.
When freeze
protecon is
acve, this icon will
be illuminated.
Freeze Protecon Operaon
When the boiler detects low outdoor ambient
temperatures, the boiler will begin its freeze
protecon operaon. The freeze protecon
operaon can protect the boiler from freezing
down to as low as 22°F (-30°C) outdoor
ambient temperature.
When freeze protecon is in operaon, the
pump may circulate water and/or the boiler
may dry re to prevent the boiler from freezing.
Ensure power and gas are supplied to the boiler
for freeze protecon to funcon. The internal
freeze protecon will not necessarily prevent
the system piping from freezing.
During freeze protecon operaon, the
pressure and supply temperature will
alternately display on the controller.
When the system needs to be shutdown for
extended periods of me, the power and gas
supply should be disconnected from the boiler.
The boiler and all system piping should then be
drained. Freezing damage may occur if there is
water remaining in the boiler or system piping.
The plumbing lines should also be blown out
via compressed air.
20
PSI