Installation Manual
110 Rinnai I-Series Condensing Boiler Solo Manual
When replacing an exisng boiler, the
heang system shall be ushed with an
approved system cleaner before the new
boiler is added to the system.
The Rinnai boiler must be isolated from the
system while the system is ushed. No
system cleaner should ever enter the boiler
heat exchanger due to its causc nature
which could damage the heat exchanger.
Reference secon “14.1 Approved
Cleaners, Inhibitors and Anfreezes” in the
Appendix for an approved list of system
cleaners, inhibitors, and anfreezes.
Instrucons
1. Flush the CH system with water.
2. Isolate the boiler from the CH system.
3. Fill the CH system with an approved
cleaner and circulate through the system.
4. If the installaon is a zone system (ulizes
mulple zones), ush out each zone
individually.
5. Flush the CH system with water again,
ensuring all zones have been ushed.
6. Clean out the dirt trap per manufacture’s
instrucons.
7. The boiler and system may now be lled
through the ll valves.
8. If using glycol, ensure it is an approved
glycol and rao.
9. Verify water quality is within the stated
values in secon “4.4.1 Water Quality
Guidelines.”
IMPORTANT
• Water should be within guidelines for
water quality listed in secon “4.4.1
Water Quality Guidelines.”
• Use the proper water treatment to
ensure the pH and water hardness are
within the Rinnai boiler water quality
guidelines listed in secon “4.4.1 Water
Quality Guidelines.”
• Test the pH of the water that will be
used for lling the system.