Installation Manual
54 Rinnai I-Series Condensing Boiler Solo Manual
Rinnai requires the use of hydraulic separaon between the boiler and central heang system.
Hydraulic separaon and primary/secondary piping allow two or more circulators in a hydronic
system to operate independently, without interfering with ow in connecng piping circuits.
Distance no
more than four
pipe diameters
IMPORTANT
For closely spaced tee installaons, the
separaon at the header is to be no
more than four pipe diameters.
Closely Spaced Tees
Boiler Supply
Boiler Return
NOTE
Examples of Hydraulic Separaon
Closely spaced tees and low loss headers are common examples of hydraulic separators and are
used to separate the boiler loop from the central heang loop.
When Rinnai I-Series Boilers are in use with Rinnai air handlers, please reference the air handler
Installaon and Operaon Manual for installaon and performance details.