Installation Manual
56 Rinnai I-Series Condensing Boiler Solo Manual
The I-Series Solo Boiler does not have an included a boiler pump. An external boiler pump must be
installed and sized to the ow rate and pressure drop through the boiler, system piping, and system
components. Larger systems, or systems with large pressure drops, should incorporate a form of
hydraulic separaon, such as closely spaced tees or a low loss header.
Below are opons for the primary pump circulang across the boiler. No addional pressure drop is
accounted for through the system piping or system components. Recommended circulaon pumps
are listed below. The maximum amperage permied is 2 Amps.
Manufacturer part numbers are correct at me of publicaon and are subject to change without
noce. Contact manufacturer to conrm performance and part number prior to placing an order.
Model
Pump Model
Grundfos Taco Bell & Gosse Armstrong
i060S UPS 15-42 007-IFC NRF-25 ASTRO 230CI
i090S UPS 15-42 007-IFC NRF-25 ASTRO 230CI
i120S UPS 15-58 008-IFC NRF-25 ASTRO 230CI
i150S UPS 26-99 0011-IFC N/A ASTRO 280CI
i060S and i090S
i120S and i150S
Water Flow (GPM)
Pressure Loss (Feet of Head)