Installation Manual
62 Rinnai I-Series Condensing Boiler Solo Manual
NOTE
When DIP Switch 3 is in the OFF (default) posion Parameter 32 becomes available. The opon to
select an indirect tank pump (default) or a 3-Way Valve with the boiler pump for recovering the
indirect tank becomes available. If the 3-Way Valve opon is desired, only 120VAC 3-Way Valves
may be used. Do not use a 3-Way Valve if simultaneous CH and DHW via an indirect tank is desired.
1. Remove the boiler’s front panel by removing the four screws that secure the panel.
2. Locate the PC Board (lower le side of unit).
3. Connect the indirect tank thermistor to the terminals shown below using minimum 18 AWG
wiring to the two terminals provided in the enclosure.
4. Locate the DIP switches on the PC Board (see below). Ensure that DIP switch 3 is in the OFF
(default) posion (this ensures the boiler will operate the indirect tank recirculaon pump
connected to the Pump 2 connecon).
5. Adjust DIP switch 4 to one of the following:
• OFF (default) for thermistor control of the indirect tank
• ON for thermostat control on the indirect tank
6. Set parameters 30-35 as appropriate for your applicaon (see the Parameter Sengs Table for
more informaon).
Indirect Tank Thermistor Connecon
PC
Board
DIP Switches
ON
OFF
Indirect Tank
Thermistor Connecon
Indirect Tank Pump
Connecon
Indirect tank pump
to be wired to boiler.
• Refer to secon “9.2 Electrical Connecons” for more informaon on the boiler’s electrical connecons.
• Refer to secon “12.3.8 PC Board DIP Switches” for more informaon on the boiler’s DIP switches.