Installation Manual
Rinnai I-Series Condensing Boiler Solo Manual 65
Parameter
Number
Seng Descripon
Selecon
A b C d
Indirect Tank Supply
Temperature with Thermistor
Control
180°F
(82°C)
Seng
Temperature
+18°F
(+10°C)
Seng
Temperature
+27°F
(+15°C)
30
Indirect Tank Supply
Temperature with Thermostat
Control
180°F
(82°C)
160°F
(71°C)
140°F
(60°C)
31
Allowed Indirect Tank
Temperature Drop before
Firing (with Thermistor)
5.4°F
(3°C)
10.8°F
(6°C)
16.2°F
(9°C)
21.6°F
(12°C)
32
Indirect Tank Operaon Opon Use Pump Use 3-Way
Valve
33
Indirect Tank Simultaneous
Heang
Indirect Tank
Priority
Simultaneous
Heang with
Indirect Tank
and CH
34
Indirect Tank Priority Time 60
minutes
40
minutes
90
minutes
35
CH Temperature Limitaon to
Allow Simultaneous Operaon
with Indirect Tank
Yes No
NOTE
Refer to secon “12.4.1 Parameter Sengs Table” for more informaon on parameter sengs.