Installation Manual
Rinnai I-Series Condensing Boiler Solo Manual 87
Thermostat Usage (Default Seng)
This is the default seng for the boiler. This seng enables the boiler to operate in CH from a call
for heat from the room thermostat or zone controller. In this seng, the Central Heang buon is
not funconal except as an Error Reset or other seng.
This seng enables the boiler to operate via the Central Heang buon being acve
(illuminated). While the Central Heang buon is ON, the boiler operates
connuously or unl the return sensor on the boiler gives the signal to cycle o. The
burner res up only when supply or return water temperature reduces. This seng
should be disabled when CH is no longer seasonally needed.
To select Thermostat Usage or the Central Heang buon, follow the steps below:
1. Remove the boiler’s front panel by removing the four screws that secure the panel.
2. Locate the PC Board (lower le side of unit). Locate the DIP switches on the PC Board
(see below).
3. Adjust DIP switch 2 to one of the following posions
• ON - Central Heang ON buon used. Boiler res based on return water temperature
• OFF (Default) - Thermostat Used
4. Press the CH buon on the controller display. The boiler is now in CH mode.
ON
OFF
DIP Switches
PC Board
Pump Linkage with CH Mode On
When CH Mode is acve, Parameter 41 becomes available. Parameter 41 enables a system pump to
be linked with the boiler pump. When Parameter 41 is selected as “b,” the two pumps will run at the
same me.
Parameter
Number
Seng Descripon
Selecon
A b
41
Linked Operaon Between Main Boiler Pump and CH Pump 1
No
Yes (Linked
Together)
This parameter is only in use when DIP switch 2 is in the ON
posion. This enables the linked operaon between the main
boiler pump and CH pump 1. For example, when the main
pump is on, pump 1 is also on. When DIP switch 2 is in the
OFF posion, the pumps are automacally linked.
Central Heang
buon
Central Heang Buon
IMPORTANT
Central Heang Mode on the I-Series Boiler is not designed for typical room thermostat control
systems. Central Heang Mode runs the pump(s) and heat constantly and ignores room thermostat
input. This mode may/will overheat zones not equipped with constant recirculaon temperature
control (such as thermostac heads).