Installation Manual
90 Rinnai I-Series Condensing Boiler Solo Manual
Parameter
Number
Seng Descripon
Selecon
A b C d
30
Indirect Tank Supply Temperature with
Thermostat Control
180°F
(82°C)
160°F
(71°C)
140°F
(60°C)
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3 and
when Indirect Tank Control "Thermostat"
selected on DIP switch 4.
This selects the supply temperature for the
indirect tank when using a thermostat. 180°F
(Default) is the maximum supply temperature.
The higher the supply temperature to the tank,
the quicker the tank will heat up. If this
temperature is too high, select other sengs as
appropriate. Ensure the indirect tank supply
temperature is 18°F (10°C) higher than the set
point temperature of the tank thermostat.
Indirect Tank Supply Temperature with
Thermistor Control
180°F
(82°C)
Seng
Temperature
+18°F
(+10°C)
Seng
Temperature
+27°F
(+15°C)
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3 and
when Indirect Tank Control "Thermistor"
selected on DIP switch 4.
This selects the supply temperature for the
indirect tank when using a thermostat. 180°F
(Default) is the maximum supply temperature.
The higher the supply temperature to the tank,
the quicker the tank will heat up. If this
temperature is too high, select other sengs as
appropriate.
31
Allowed Indirect Tank Temperature Drop before
Firing (with Thermistor)
5.4°F
(3°C)
10.8°F
(6°C)
16.2°F
(9°C)
21.6°F
(12°C)
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3 and
when Indirect Tank Control "Thermistor"
selected on DIP switch 4.
This selects the dierenal temperature
between the indirect tank setpoint temperature
and thermistor reading. The smaller the value,
the more frequently the indirect tank will call
for heat.
Connued on next page