Installation Manual
Rinnai I-Series Condensing Boiler Solo Manual 91
Parameter
Number
Seng Descripon
Selecon
A b C d
32
Indirect Tank Operaon Opon
Use Pump
Use 3-Way
Valve
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3. When
a 3 Way Valve and the boiler pump are to be
used for recovering the indirect tank select “b”.
Only 120 VAC 3 Way Valves may be used in this
applicaon.
33
Indirect Tank Simultaneous Heang
Indirect
Tank
Priority
Simultaneous
Heang with
Indirect Tank
and CH
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3 and
when "Use Pump" is selected in Parameter 32.
This selects the operaon of the indirect tank
heang by priority or simultaneously with CH.
When "Indirect Tank Priority" is selected, other
pumps except for the indirect tank pump will
not operate while the tank is being heated.
When "Simultaneous Heang with Indirect Tank
and CH", all pumps may operate simultaneously.
When in Simultaneous mode, if the tank does
not achieve the Indirect Tank Setpoint
Temperature within 60 minutes, it will transion
to Indirect Tank Priority.
34
Indirect Tank Priority Time
60
minutes
40
minutes
90
minutes
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3. This
selects the me that the indirect tank will
maintain priority. Aer this period of me
passes, the indirect tank will cease to be heated
and central heang will have priority. If there is
sll an indirect tank demand aer 60 minutes
passes of CH priority, indirect tank priority will
begin again.
35
CH Temperature Limitaon to Allow
Simultaneous Operaon with Indirect Tank
Yes No
*This parameters is available when Indirect
Tank "In Use" is selected on DIP switch 3 and
when "Use Pump" is selected in Parameter 32
and also when selecng "Simultaneous Heang
with Indirect Tank and CH" in Parameter 33.
This enables CH seng limitaon during
simultaneous heang. This can prevent
unintenonally supplying high temperature
supply water to low water heang temperature
applicaons such as oor heang. During
simultaneous operaon, the heang supply
temperature is based on the indirect tank
supply temperature. When "NO" is selected,
make sure that the CH system and heang
applicaon is designed to allow for the high
supply temperature.